| Date |
Text |
| 2007-05-24 15:38:07 | *** DENIED *** |
| | 1) A/C EQUIPMENT LISTING ON MECHANICAL PLANS A/C #1 IS |
| | SHOWING THE WRONG TOTAL AND SENSIBLE BTU'S. AND A/C #2 |
| | IS NOT SHOWING ANY TOTAL AND SENSIBLE BTU'S. PLEASE |
| | CORRECT BOTH. |
| | |
| | 2) PLEASE SHOW SEER FOR A/C UNITS IN EQUIPMENT |
| | LISTING. |
| | |
| | 3) PLEASE SUBMIT THE "LONG FORM" SHOWING THE |
| | CALCULATIONS FOR THE COOLING LOAD CALCULATIONS OR YOU |
| | MAY SUBMIT A MANUAL J CALCULATION, SEE 2004 FBC |
| | 13-607.1.ACB.1. |
| | |
| | 4) PLEASE SUBMIT DETAILED MANUFACTURER'S |
| | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR GAS |
| | GRILL UNDER COVERED LOGGIA AS IT MAY NEED AN APPROVED |
| | EXHAUST HOOD. |
| | |
| | 5) MECHANICAL PLANS SECOND FLOOR SHOW NO SUPPLY AIR |
| | DUCT GOING TO THE 8X6 SUPPLY GRILL IN HER CLOSET |
| | (MASTER SUITE) PLEASE CORRECT. |
| | |
| | 6) THE 12" RETURN AIR TRANSFER DUCT TO THE MASTER SUITE |
| | NEEDS TO BE 18", SEE 2004 FBC/R M1602.4 (A) AND (C) |
| | EXCEPT. |
| | |
| | *** 2004 FBC/R M1602.4.BALANCED RETURN AIR MAY BE |
| | ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE |
| | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS |
| | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR |
| | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO |
| | ACHIEVE PROPER RETURN AIR BALANCE. |
| | (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET |
| | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR |
| | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY |
| | ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE |
| | SHALL BE INCLUDED. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |