Plan Review Notes
Plan Review Notes For Permit 07010127
Permit Number 07010127
Review Stop E
Sequence Number 2
Notes
Date Text
2007-04-04 07:38:37 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THIS COMMENT WAS ON THE PEVIOUS REVIEW.
  
 1}PLEASE SUBMIT DETAILS FOR THE PANEL SHOWN ON THE
 SCHEMATIC, FEEDER AND CONDUIT SIZE AND TYPE, PANEL
 RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC. IF THIS PANEL IS
 EXISTING, INDICATE SAME, IT APPEARS TO BE A NEW
 INSTALLATION WHICH IS THE REASON FOR THIS COMMENT.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]