| 2007-01-18 11:20:53 | DENIED |
| | REFERENCE: FBC-2004 SECTION 424 & R4101 |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| | PLAN REVIEW TO MEET CODE COMPIANCE: |
| | |
| | 1) FBC-2004 SEC. 424.2.6.6.5, OR |
| | FBCR-2004 SEC. R4101.6.6.5 WHERE |
| | PROVIDED, THE VACUUM OR PRESSURE CLEANER |
| | FITTING SHALL BE LOCATED AT LEAST 6" AND |
| | NOT GREATER THAN 12" BELOW THE MINIMUM |
| | OPER- ATING WATER LEVEL OR AS AN |
| | ATTACHMENT TO THE SKIMMER.(DETAIL |
| | REQUIRED WITH MODEL NUMBER OR SUBMIT MANUFACTURER CUT |
| | SHEET) |
| | |
| | 2) FBC-2004 SEC. 424.2.14.1, OR |
| | FBCR-2004 SEC. R4101.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. (MANUFACTURE |
| | SHEETS REQUIRED, PLEASE SUBMIT) |
| | |
| | 3) FBC-2004 SEC. 424.2.14.2, OR |
| | FBCR-2004 SEC. R4101.14.2 WATER |
| | RETENTION, PROVIDE A POSITIVE MEANS OF |
| | RETAINING WATER IN THE HEATER WHEN PUMP |
| | IS SHUT OFF.(MANUFACTURE SHEETS |
| | REQUIRED, PLEASE SUBMIT) |
| | |
| | 4) FBC-2004 SEC. 424.2.7.2, OR |
| | FBCR-2004 SEC. R4101.7.2 PUMPS AND |
| | EQUIPMENT SHALL BE MOUNTED ON A |
| | SUBSTANTIAL BASE IN A MANNER THAT WILL |
| | ELIMINATE STRAIN ON PIPING.SLAB SHALL |
| | BE A NOMINAL 4" THICK. (PLEASE INDICATE POOL EQUIPMENT |
| | SLAB THICKNESS ON THE RESUBMITTED DETAIL ON SHEET 3 OF |
| | 4) |
| | |
| | END OF COMMENTS: |
| | |