2007-01-17 08:01:14 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1}PLEASE SUBMIT DETAILS FOR THE PANEL SHOWN ON THE
 SCHEMATIC, FEEDER AND CONDUIT SIZE AND TYPE, PANEL
 RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC. IF THIS PANEL IS
 EXISTING, INDICATE SAME, IT APPEARS TO BE A NEW
 INSTALLATION WHICH IS THE REASON FOR THIS COMMENT.
  
 2} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE. SEE ARTICLE 680.26 AFFECTING BONDING AND
 EQUIPOTENTIAL BONDING.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.