| Plan Review Notes For Permit 07010127 |
| Permit Number |
07010127 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-17 08:01:14 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW | | | | | | 1}PLEASE SUBMIT DETAILS FOR THE PANEL SHOWN ON THE | | | SCHEMATIC, FEEDER AND CONDUIT SIZE AND TYPE, PANEL | | | RATING AND OCP, | | | PANEL SCHEDULE AND COMPUTED LOAD, ETC. IF THIS PANEL IS | | | EXISTING, INDICATE SAME, IT APPEARS TO BE A NEW | | | INSTALLATION WHICH IS THE REASON FOR THIS COMMENT. | | | | | | 2} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE | | | EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS | | | PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT | | | TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS | | | CHANGE. SEE ARTICLE 680.26 AFFECTING BONDING AND | | | EQUIPOTENTIAL BONDING. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|