| Date |
Text |
| 2007-01-14 16:51:00 | |
| | ** UNSAT ** |
| | |
| | 1) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON |
| | PLANS FOR THE DESIGNS WHICH THEY ARE UNDER. |
| | PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER |
| | DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE |
| | RELEVANT. |
| | 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70 |
| | (NEC). |
| | |
| | |
| | 2) NOTE: PLEASE SEE ONE SET OF THE PLANS ARE |
| | PHOTO-COPIES OF SIGNED AND SEALED PLANS. |
| | PLEASE SEE THE FAC 61G15-23.002 AND FS 471.025 WHICH |
| | REQUIRES BOTH SETS TO BE SIGNED, DATED AND SEALED AS |
| | ORIGINAL. |
| | THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SHOW EITHER EXISTING OR NEW TO BE |
| | PROVIDED BATTERY BACK UP EMERGENCY LIGHT OF SOME KIND |
| | REQUIRED FOR EGRESS. |
| | LS 101 7.8, 7.9. |
| | NEC 700.16, 700.12E. |
| | |
| | 4) NOTE: PLEASE KNOW IF THIS BUILDING WHICH MOST LIKELY |
| | CONTAINS A FIRE ALARM SYSTEM, SHOULD SHOW NEW OR |
| | EXISTING, HORNS, STROBES OR HORN/STROBES WHICH MEET THE |
| | MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND 3(4) FOR ADA. |
| | THIS SCOPE OF WORK IS CREATING ADA COMPLIANT BATHROOMS, |
| | PLEASE SHOW FOR COMPLIANCE. |
| | PLEASE SHOW THE DEVICES AND LEVELS. |
| | PLEASE KNOW THAT ANY ADDITIONS TO THE FIRE ALARM WILL |
| | ALSO BE REQUIRED TO BE UNDER A SEPARATE PERMIT HOWEVER |
| | THESE BASE SYSTEM DEVICES ARE REQUIRED AT THIS TIME. |
| | FBC 106.3.5.1.2 ADMIN SECTION. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |