| 2007-02-06 09:22:52 | DENIED |
| | REFERENCE: FBC-2004 SECTIONS 424.2 AND R4101 SWIMMING |
| | POOLS |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| | PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1) FBC-2004 SEC. 424.2.6.6.5, OR |
| | FBCR-2004 SEC. R4101.6.6.5 WHERE |
| | PROVIDED, THE VACUUM OR PRESSURE CLEANER |
| | FITTING SHALL BE LOCATED AT LEAST 6" AND |
| | NOT GREATER THAN 12" BELOW THE MINIMUM |
| | OPER ATING WATER LEVEL OR AS AN |
| | ATTACHMENT TO THE SKIMMER. |
| | NOTE: PLEASE PROVIDE MANUFACTURER SPECIFICATION SHEET |
| | OR INDICATE THE MAKE AND MODEL NUMBER ON THE |
| | RESUBMITTED PRINTS. |
| | |
| | 2) FBC-2004 SEC. 424.2.7.2, OR |
| | FBCR-2004 SEC. R4101.7.2 PUMPS AND |
| | EQUIPMENT SHALL BE MOUNTED ON A |
| | SUBSTANTIAL BASE IN A MANNER THAT WILL |
| | ELIMINATE STRAIN ON PIPING.SLAB SHALL |
| | BE A NOMINAL 4" THICK. |
| | NOTE: (DETAIL REQUIRED) |
| | |
| | 3) FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC. |
| | R4101.9 WATER SUPPLY, LOCAL ORD. |
| | #2853-95, BACKFLOW REQUIRED ON WATER |
| | SERVICE.(ADD TO NOTES) |
| | |
| | 4) FBC-2004 SEC. 424.2.12.1, OR |
| | FBCR-2004 SEC. R4101.12.1 PRESSURE |
| | TESTS. PER MANUFACTURE RECOMMENDATIONS, |
| | NO AIR TEST SHALL BE APPROVED FOR PVC |
| | PIPE AND FITTINGS. (ADD TO NOTES) |
| | |
| | 5) FBC-2004 SEC. 424.2.13.2, OR |
| | FBCR-2004 SEC.R4101.13.2 JOINTS AND |
| | CONNECTIONS, FBC PLMG SEC 605.21, PURPLE |
| | PRIMER REQUIRED ON PVC PIPING.(ADD TO |
| | NOTES) |
| | |
| | 6) SHEET 1 SPECIFICATIONS POOL HEATER TYPE, PLEASE |
| | INDICATE FUTURE STUB-OUT. SHEET 2 POOL PIPING DIAGRAM, |
| | PLEASE INDICATE FUTURE HEATER STUB-OUT AND INDICATE |
| | THAT THE HEATER STUB-OUTS ARE BEING PRESSURE CAPPED. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |