| Plan Review Notes For Permit 07010010 |
| Permit Number |
07010010 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-01-09 15:41:37 | REVISION: GAS PRESSURE INCREASED TO 2PSI AND MP | | | REGULATORS INSTALLED AS INDICATED. | | | | | | **********PROVISO | | | FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE | | | GEN/RES PERMIT REQUIRED WITH ZONING, ELECTRICAL AND GAS | | | APPROVAL OF GENERATOR PLACEMENT. PER FBC-2004 FUEL GAS, | | | SECTION 404.12 GAS CONNECTIONS THAT DO NOT CONNECT TO | | | APPLIANCES SHALL BE CAPPED GAS TIGHT. | | | | | | IF WATER HEATER ROOM IS A CONFINED SPACE, OPENINGS | | | REQUIRED PER SECTION 304.5 OR SECTION 304.6 SHALL BE | | | INSTALLED. | | | MINIMUM 3,755 CUBIC FEET REQUIRED. |
|