Plan Review Notes
Plan Review Notes For Permit 06120723
Permit Number 06120723
Review Stop P
Sequence Number 2
Notes
Date Text
2007-05-10 08:59:30****************PROVISO****************
 FBC-2004 PLUMBING
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
 (B) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 (E) FIXTURES TO BE SIZED PER FBC-2004 PLUMBING SECTIONS
 416.3 LAVATORY WASTE OUTLETS, 417.3 SHOWER WASTE
 OUTLETS AND 420.4 WATER CLOSET CONNECTIONS.