Plan Review Notes
Plan Review Notes For Permit 06120723
Permit Number 06120723
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-10 08:06:26 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), SHOW SAME ON THE PANEL SCHEDULE.
  
 3} 230.70 GENERAL.
 MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN
 A BUILDING OR OTHER STRUCTURE FROM THE SERVICE-ENTRANCE
 CONDUCTORS.INDICATE COMPLIANCE WITH THIS ARTICLE BY
 STATING THE PANEL COMPLIES (HAS A 200 AMP MAIN
 BREAKER), OR A DISCONNECTING MEANS AT THE METER.
  
 4} GIVE PANEL SPECIFICATIONS, NUMBER OF SPACES, VOLTAGE
 AND AMPERE RATING, MAIN LUG OR MAIN BREAKER.
  
 5} SHEET A-1 NOTES REWIRING THE WHOLE HOUSE W/NEW 200
 AMP PANEL, SHEET A-2 NOTE AN EXISTING PANEL. PLEASE
 CORRELATE.
  
 6} IF THE CUSTOMARY RECEPTACLE SYMBOL, THAT IS LOCATED
 BEHIND THE WATER HEATER AND CONDENSING UNITS, IS
 SUPPOSED TO REPRESENT THE REQUIRED DISCONNECTS FOR
 SAME, THEY ARE IN VIOLATION OF 110.26 FOR CLEAR SPACE.
  
 7} LOCATE THE REQUIRED DISCONNECTING MEANS FOR THE
 WATER HEATER AND THE CONDENSING UNIT. 422.30 & 440.14.
  
 8} SHOW COMPLIANCE WITH THE REQUIRED A/CRECEPTACLE
 PER 210.63.
  
 9} THE RANGE MUST BE CALCULATD @ 8KW MINIMUM PER
 220.55.
  
 10} NOTE THE DOWNSTAIRS BEDROOM RECEPTACLE ADJACENT TO
 THE ENTRY, NEEDS TO BE MOVED OR ANOTHER ADDED TO COMPLY
 WITH 210.52(A)(1).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  
  
  
  