| 2007-01-04 11:11:08 | *****REDLINED PLANS.******* |
| | |
| | |
| | |
| | ** SET OF ELECTRICAL PLANS STMAPED 1/04/07 IS FOR UNDER |
| | GROUND INSTALLATIONS OF ELECTRICAL CONDUITS FOR MAIN |
| | ELECTRICAL DISTRIBUTION SYSTEM, AND ANY STUB UP |
| | LOCATIONS FOR FUTURE BRANCH CIRCUIT POWER/LIGHTING AND |
| | LOW VOLTAGE LOCATIONS. |
| | |
| | ** SHEETS REDLINED FOR ATTACHMENTAND INSTALLATION OF |
| | ALLGROUNDING ELECTRODE SYSTEM CONDUCTORS FOR THE MAIN |
| | SYSTEM AND STUB UPS FOR FUTURE GROUNDING ELECTRIDE |
| | RISER. THIS IS INCLUSIVE OF THE UNDERGROUND SLAB |
| | ATTACHMENTS FOR THE LIGHTNING PROTECTIONSYSTEM |
| | UNDERGROUNDS. DETAILS AND NOTES ARE ON PLANS. |
| | |
| | ** SHEETS ALSO INCLUDE INSTALLATION OF MANHOLES AND |
| | DUCT BANKS TO EACH SECTION OF OF THE SITE. |
| | |
| | ELECTRICAL CONTRACTOR(S)/ CERTIFIED LIGHTNING |
| | PROTECTION INSTALLATION CONTRACTOR(S)FOR SCOPE OF |
| | WORK FOR MAIN ELECTRICAL SYSTEM AND ANY LIGHTNING |
| | PROTECTION MAY REFERENCE THESE PLANS AND PERMIT NUMBER |
| | FOR THEIR SCOPE OF WORK. LIGHTING PROTECTION WORK FOR |
| | FOUNDATION WILL BE A SEPARATE ELECTRICAL PERMIT FROM |
| | THE MAIN ELECTRICAL UNDERGROUND SCOPE. |
| | |
| | THIS PERMITTED SET OF PLANS FOR FOUNDATION DOES NOT |
| | INCLUDE ANY REVIEWS FOR THE BUILDING MAIN ELECTRICAL |
| | SYSTEM, ONLY THAT FOR CONDUIT SIZES AND NOTES ABOVE. |
| | |
| | ALL THREE SETS STAMPED |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2007-01-04 06:54:22 | 2007-01-04 06:54:22 |
| | IN ELEC FOR REVIEW |