Plan Review Notes
Plan Review Notes For Permit 06120699
Permit Number 06120699
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-01-24 14:46:19***DENIED***
  
 1) STANDPIPE CONNECTIONS ARE LOCATED AT ALTERNATE STAIR
 LEVELS WHICH WILL NOT BE AN ACCEPTABLE ARRANGEMENT.
 CONNECTIONS SHALL BE LOCATED AT EACH LEVEL OF FLOOR
 ENTRANCE.
  
 2) STANDPIPE CONNECTIONS TO BE 2 1/2"- 1 1/2" REDUCER
 WITH CHAIN.
  
 3) STANDPIPE CONNECTIONS SHALL BE LOCATED SO AS NOT TO
 INTERFERE WITH MEANS OF EGRESS.
  
 4) IT WOULD APPEAR THAT THE GROUND LEVEL CONNECTION IS
 LOCATED IN A MANNER THAT NEGATIVELY IMPACTS REQUIRED
 HEADROOM DISTANCE.
  
 5) STANDPIPE CONNECTIONS SHALL BE LOCATED NOT TO EXCEED
 130'.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW