| Plan Review Notes For Permit 06120699 |
| Permit Number |
06120699 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-24 14:46:19 | ***DENIED*** | | | | | | 1) STANDPIPE CONNECTIONS ARE LOCATED AT ALTERNATE STAIR | | | LEVELS WHICH WILL NOT BE AN ACCEPTABLE ARRANGEMENT. | | | CONNECTIONS SHALL BE LOCATED AT EACH LEVEL OF FLOOR | | | ENTRANCE. | | | | | | 2) STANDPIPE CONNECTIONS TO BE 2 1/2"- 1 1/2" REDUCER | | | WITH CHAIN. | | | | | | 3) STANDPIPE CONNECTIONS SHALL BE LOCATED SO AS NOT TO | | | INTERFERE WITH MEANS OF EGRESS. | | | | | | 4) IT WOULD APPEAR THAT THE GROUND LEVEL CONNECTION IS | | | LOCATED IN A MANNER THAT NEGATIVELY IMPACTS REQUIRED | | | HEADROOM DISTANCE. | | | | | | 5) STANDPIPE CONNECTIONS SHALL BE LOCATED NOT TO EXCEED | | | 130'. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | (561) 805-6722 OR 804-4756 |
|