Plan Review Notes
Plan Review Notes For Permit 06120693
Permit Number 06120693
Review Stop M
Sequence Number 2
Notes
Date Text
2007-08-28 16:34:02PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 1-2-07 NOTE #4, MANUAL J
 CALCULATION DO NOT SHOW THE BUILDINGS NEEDED SENSIBLE
 BTU'S ON THEM, (THE HIGH LIGHTED SENSIBLE BTU'S ARE FOR
 THE A/C SYSTEM NOT THE BUILDING) YOU MAY NEED THE LONG
 FORM TO GET THIS, PLEASE CORRECT
  
 2) THE GAS CLOTHES DRYER APPEARS TO BE GETTING IT'S
 COMBUSTION AIR FROM THE SECOND FLOOR BATHROOM, PER RES.
 M1701.4 PROHIBITED SOURCES.
 COMBUSTION AIR DUCTS AND OPENINGS SHALL NOT CONNECT
 APPLIANCE ENCLOSURES WITH SPACE IN WHICH THE OPERATION
 OF A FAN MAY ADVERSELY AFFECT THE FLOW OF COMBUSTION
 AIR. COMBUSTION AIR SHALL NOT BE OBTAINED FROM AN AREA
 IN WHICH FLAMMABLE VAPORS PRESENT A HAZARD. FUEL-FIRED
 APPLIANCES SHALL NOT OBTAIN COMBUSTION AIR FROM ANY OF
 THE FOLLOWING ROOMS OR SPACES:
 1.SLEEPING ROOMS.
 2.BATHROOMS.
 3.TOILET ROOMS.
 PLEASE SHOW THE COMBUSTION AIR CALCULATIONS FOR THE GAS
 CLOTHES DRYER AND PROVIDE COMBUSTION AIR IN COMPLIANCE
 WITH M1701.1, M1701.2, AND M1701.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]