| 2007-08-28 16:34:02 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA |
| | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). |
| | |
| | *** DENIED *** |
| | 1) AS NOTED IN LAST REVIEW 1-2-07 NOTE #4, MANUAL J |
| | CALCULATION DO NOT SHOW THE BUILDINGS NEEDED SENSIBLE |
| | BTU'S ON THEM, (THE HIGH LIGHTED SENSIBLE BTU'S ARE FOR |
| | THE A/C SYSTEM NOT THE BUILDING) YOU MAY NEED THE LONG |
| | FORM TO GET THIS, PLEASE CORRECT |
| | |
| | 2) THE GAS CLOTHES DRYER APPEARS TO BE GETTING IT'S |
| | COMBUSTION AIR FROM THE SECOND FLOOR BATHROOM, PER RES. |
| | M1701.4 PROHIBITED SOURCES. |
| | COMBUSTION AIR DUCTS AND OPENINGS SHALL NOT CONNECT |
| | APPLIANCE ENCLOSURES WITH SPACE IN WHICH THE OPERATION |
| | OF A FAN MAY ADVERSELY AFFECT THE FLOW OF COMBUSTION |
| | AIR. COMBUSTION AIR SHALL NOT BE OBTAINED FROM AN AREA |
| | IN WHICH FLAMMABLE VAPORS PRESENT A HAZARD. FUEL-FIRED |
| | APPLIANCES SHALL NOT OBTAIN COMBUSTION AIR FROM ANY OF |
| | THE FOLLOWING ROOMS OR SPACES: |
| | 1.SLEEPING ROOMS. |
| | 2.BATHROOMS. |
| | 3.TOILET ROOMS. |
| | PLEASE SHOW THE COMBUSTION AIR CALCULATIONS FOR THE GAS |
| | CLOTHES DRYER AND PROVIDE COMBUSTION AIR IN COMPLIANCE |
| | WITH M1701.1, M1701.2, AND M1701.4. |
| | |