| Date |
Text |
| 2007-08-24 19:11:31 | |
| | *** DENIED2ND REVIEW *** |
| | |
| | *** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS |
| | BASED ON SOME INFORMATION ON REVISED PLANS. |
| | |
| | ** SEVERAL OF THE ITEMS BELOW WOULD HAVE BEEN REDLINED |
| | HOWEVER A COUPLE OF COMMENTS ARE NEEDED AT THIS TIME |
| | AND PLANS ARE COMING BACK FOR OTHER COMMENTS. PLEASE |
| | ADDRESS ALL AT THIS TIME EVEN AS MANY OF THESE WERE |
| | ITEMS WHICH WOULD HAVE BEEN REDLINED. |
| | |
| | 1) NOTE: PLEASE SEE THE CODE REFERENCES *2005 |
| | NFPA-2005*. THIS APPEARS TO BE A MISPRINT AND WOULD |
| | HAVE BEEN REDLINED. SEE PLANS. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO |
| | RECESSED LIGHTING FIXTURES WHICH ARE REQUIRED TO MEET |
| | FBC 13-606.1.ABC.1.2.4. THE INCORRECT CODE SECTION WAS |
| | GIVEN BY THIS REVIEWER ON PREVIOUS REVIEW, HOWEVER THE |
| | TYPE OF FIXTURES ARE STILL REQUIRED. |
| | RESPONSE MENTIONS TO SEE REVISED LEGEND HOWEVER COULD |
| | NOT LOCATE ANY REFERENCE TO THE TYPE OF FIXTURES. |
| | |
| | 3) NOTE: PLEASE SEE THE PANEL/SERVICE LOAD CALCULATIONS |
| | ARE BLANK AND NOT COMPLETE AT THIS TIME. |
| | PLEASE SEE NEC 220 FOR CALCULATIONS. |
| | PLEASE CLARIFY RECESSED LIGHTING FIXTURES IN LOAD |
| | CALCULATIONS AS THESE WITH THE AMOUNT SHOWN ON PLANS |
| | MAY NOT BE FIGURED IN THE GENERAL LIGHTING LOADS.220.14 |
| | |
| | MAY CALL TO GO OVER THIS. |
| | |
| | 4) NOTE: PLEASE SEE 210.52 FOR A MISSING RECEPTACLE |
| | UPSTAIRS BEDROOM. |
| | THIS WOULD HAVE BEEN REDLINED ALSO. |
| | |
| | 5) NOTE: PLEASE PROVIDE ALL ROOM AND AREA DESIGNATIONS |
| | ON PLANS. THIS IS TO COORDINATE WITH THE PANEL SCHEDULE |
| | AS ALREADY SUBMITTED. 408.4 |
| | |
| | 6) NOTE: PLEASE SEE 220.53, 210.52B1, 210.11C AS THE |
| | DINING ROOM RECEPTACLES ARE TO BE ON ONE OR *MORE* OF |
| | THE SMALL APPLIANCE CIRCUITS. THE LOAD FOR EACH SMALL |
| | APPLIANCE CIRCUIT IS REQUIRED TO BE FIGURED AT 1.5KW. |
| | PLEASE KNOW THE TWO MINIMUM ARE ALREADY SHOWN AT 1.5, |
| | HOWEVER THE DINING ROOM IS SHOWN AT .85 WHICH NEEDS TO |
| | BE 1.5. |
| | PLEASE ADJUST |
| | |
| | 7) NOTE: PLEASE SEE THE SMOKE DETECTION DEVICES WERE |
| | REVISED ON PLANS TO BE LABELED AS *SMOKE ALARMS* YET |
| | THE PANEL SCHEDULE STILL INDICATES *SMOKE DETECTORS*. |
| | THIS SEEMS LIKE IT WAS MEANT TO BE CHANGED HOWEVER IF |
| | INDEED SD PLEASE CLARIFY AND ADJUST PLANS. |
| | NFPA-72 DEFINITIONS. |
| | |
| | 8) NOTE: PLEASE SEE AHU #2 AS THIS INDICATES A 50AMP |
| | OVER CURRENT PROTECTION ON ONE PHASE AND 60AMP ON THE |
| | OTHER PHASE. |
| | (MISPRINT HOWEVER PLEASE CORRECT AT THIS TIME). |
| | 424.3B. |
| | FBC 106.1.2 |
| | |
| | AS STATED ON THE PREVIOUS REVIEW: |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |