Plan Review Notes
Plan Review Notes For Permit 06120693
Permit Number 06120693
Review Stop B
Sequence Number 2
Notes
Date Text
2007-09-20 09:32:262004 FBC
 NEW SINGLE FAMILY DWELLING
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) PROVIDE TWO COPIES OF A SIGNED AND SEALED
 GEOTECHNICAL REPORT TO VERIFY THE SAFE BEARING CAPACITY
 OF THE SOIL. SEE R401.4. (CAN BE PROVISO TO SUBMIT
 AFTER DEMO)
  
 4) THE DOORS FROM THE GARAGE TO THE RESIDENCE ARE
 REQUIRED TO COMPLY WITH R309.1 OPENING PROTECTION.
 OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM
 USED FOR SLEEPING PURPOSES SHALL NOT BE PERMITTED.
 OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL
 BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 1- 3 /
 8 INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMB CORE
 STEEL DOORS NOT LESS THAN 1- 3 / 8 INCHES (35 MM)
 THICK, OR 20-MINUTE FIRE-RATED DOORS.
  
 5) THE STORAGE AREA UNDER THE STAIRS ARE REQUIRED TO
 COMPLY WITH R311.2.2 UNDER STAIR PROTECTION. ENCLOSED
 ACCESSIBLE SPACE UNDER STAIRS SHALL HAVE WALLS, UNDER
 STAIR SURFACE AND ANY SOFFITS PROTECTED ON THE ENCLOSED
 SIDE WITH 1/2 -INCH (12.7 MM) GYPSUM BOARD.
  
  
 6) SPECIFY THE LOCATION OF THE DRAFTSTOPPING REQUIRED
 BY R502.1.2 ON THE FLOOR FRAMING PLAN. SEE ITEM #18 ON
 PREVIOUS REVIEW.
  
 7) SPECIFY THE SIZE, NUMBER AND SPACING OF THE VERTICAL
 REINFORCEMENT OF THE CONCRETE BLOCK WALLS AT THE FIRST
 AND SECOND FLOORS AND THE MASONRY CHIMNEY. FBC* 106.1.2
 SEE ITEM #22 ON PREVIOUS REVIEW.
  
 8) SPECIFY THE CONNECTORS AND HANGERS FOR THE WOOD
 GIRDER TRUSSES AT THE SECOND FLOOR BALCONY. FBC*
 106.1.2
  
 9) SHEET A.0 SPECIFIES R-19 ICYNENE INSULATION AND THE
 ENERGY CALCULATIONS SPECIFY R-30. PLEASE CORRECT. SEE
 #32 FROM PREVIOUS REVIEW.
  
 10) THE PLANS SPECIFY ISONYNE (ICYNENE) ATTIC
 INSULATION THE MANUFACTURER'S SPECIFICATIONS THAT WERE
 SUBMITTED ARE FOR ANOTHER SPRAY FOAM INSULATION. PLEASE
 REVISE SHEET A.0. RATHER THAN SPECIFY A PARTICULAR
 BRAND, JUST SPECIFY SPRAY FOAM INSULATION.
  
 11) THE SPRAY FOAM ATTIC INSULATION IS REQUIRED TO BE
 BE PROTECTED BY AN IGNITION BARRIER IN COMPLIANCE WITH
 R314.5.3 ATTICS.
 WHERE ATTIC ACCESS IS REQUIRED BY SECTION R807.1 AND
 WHERE ENTRY IS MADE ONLY FOR SERVICE OF UTILITIES, FOAM
 PLASTICS SHALL BE PROTECTED AGAINST IGNITION BY
 1.5-INCH-THICK (38 MM) MINERAL FIBER INSULATION, 1 / 4
 -INCH-THICK (6.4 MM) WOOD STRUCTURAL PANELS, 3 / 8
 -INCH (9.5 MM) PARTICLEBOARD, 1/4-INCH (6.4 MM)
 HARDBOARD, 3 / 8 -INCH (9.5 MM) GYPSUM BOARD, OR
 CORROSION-RESISTANT STEEL HAVING A BASE METAL THICKNESS
 OF 0.016 INCH (0.406 MM) AND THE THERMAL BARRIER
 SPECIFIED IN SECTION R314.4 IS NOT REQUIRED. THE
 IGNITION BARRIER IS NOT REQUIRED WHERE THE FOAM PLASTIC
 INSULATION HAS BEEN TESTED IN ACCORDANCE WITH SECTION
 R314.6 .
 THE IGNITION BARRIER IS NOT REQUIRED WHEN THE FOAM HAS
 BEEN TESTED IN ACCORDANCE WITH R314.6 SPECIFIC
 APPROVAL.
 PLASTIC FOAM NOT MEETING THE REQUIREMENTS OF SECTIONS
 R314.3 THROUGH R314.5 SHALL BE SPECIFICALLY APPROVED ON
 THE BASIS OF ONE OF THE FOLLOWING APPROVED TESTS:
 FM4880, UL 1040, NFPA 286, OR UL 1715, OR FIRE TESTS
 RELATED TO ACTUAL END-USE CONFIGURATIONS. THE SPECIFIC
 APPROVAL SHALL BE BASED ON THE ACTUAL END USE
 CONFIGURATION AND SHALL BE PERFORMED ON THE FINISHED
 FOAM PLASTIC ASSEMBLY IN THE MAXIMUM THICKNESS INTENDED
 FOR USE. ASSEMBLIES TESTED SHALL INCLUDED SEAMS, JOINTS
 AND OTHER TYPICAL DETAILS USED IN THE INSTALLATION OF
 THE ASSEMBLY AND SHALL BE TESTED IN THE MANNER INTENDED
 FOR USE. SPECIFY HOW THE FOAM WILL BE PROTECTED FROM
 IGNITION ON THE PLANS OR PROVIDE ACCEPTABLE EVIDENCE OF
 THE REQUIRED TESTING.
  
 12) PLEASE REMOVE THE OLD OR EXPIRED PRODUCT APPROVALS
 FROM THE SUBMITTAL. ONLY SUBMIT PRODUCT APPROVALS THAT
 WILL BE USED. REMOVE ANY DUPLICATE PRODUCT APPROVALS.
 INDICATE WHICH PRODUCT APPROVALS ARE FOR WHICH
 OPENINGS.
  
 13) THE COMPONENT AND CLADDING PRESSURES ON S.1 FOR A
 TWO STORY BUILDING ARE WORST CASE AND DO NOT ACCOUNT
 FOR OPENING SIZE OR GARAGE DOORS. BECAUSE SEE FBC TABLE
 R301.2(2) AND TABLE R301.2(4). BECAUSE THESE PRESSURES
 ARE SPECIFIED SOME OF THE PRODUCT APPROVALS MAY HAVE
 PRESSURES THAT ARE NOT ADEQUATE. THE OVERHEAD GARAGE
 DOORS FOR EXAMPLE. PLEASE SPECIFY THE REQUIRED
 COMPONENT AND CLADDING PRESSURES AT THE OPENINGS ON THE
 PLANS.
  
 14) THE PRODUCT APPROVAL FOR THE THERMA-TRU FIBERGLASS
 DOOR REQUIRES HURRICANE PANELS FOR THE NON-IMPACT RATED
 SIDELITES. SUBMIT PRODUCT APPROVALS FOR THE STORM
 PANELS.
  
 15) SUBMIT THE NEW NOA #06-0807.07 FOR THE PGT FD 101
 FRENCH DOORS. SEE ITEM #42 FROM PREVIOUS REVIEW.
  
 16) SUBMIT THE NEW NOA #05-1129.11 FOR THE PGT CASEMENT
 WINDOWS. SEE ITEM #43 FROM PREVIOUS REVIEW.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  