| Date |
Text |
| 2007-09-20 09:32:26 | 2004 FBC |
| | NEW SINGLE FAMILY DWELLING |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) PROVIDE TWO COPIES OF A SIGNED AND SEALED |
| | GEOTECHNICAL REPORT TO VERIFY THE SAFE BEARING CAPACITY |
| | OF THE SOIL. SEE R401.4. (CAN BE PROVISO TO SUBMIT |
| | AFTER DEMO) |
| | |
| | 4) THE DOORS FROM THE GARAGE TO THE RESIDENCE ARE |
| | REQUIRED TO COMPLY WITH R309.1 OPENING PROTECTION. |
| | OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM |
| | USED FOR SLEEPING PURPOSES SHALL NOT BE PERMITTED. |
| | OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL |
| | BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 1- 3 / |
| | 8 INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMB CORE |
| | STEEL DOORS NOT LESS THAN 1- 3 / 8 INCHES (35 MM) |
| | THICK, OR 20-MINUTE FIRE-RATED DOORS. |
| | |
| | 5) THE STORAGE AREA UNDER THE STAIRS ARE REQUIRED TO |
| | COMPLY WITH R311.2.2 UNDER STAIR PROTECTION. ENCLOSED |
| | ACCESSIBLE SPACE UNDER STAIRS SHALL HAVE WALLS, UNDER |
| | STAIR SURFACE AND ANY SOFFITS PROTECTED ON THE ENCLOSED |
| | SIDE WITH 1/2 -INCH (12.7 MM) GYPSUM BOARD. |
| | |
| | |
| | 6) SPECIFY THE LOCATION OF THE DRAFTSTOPPING REQUIRED |
| | BY R502.1.2 ON THE FLOOR FRAMING PLAN. SEE ITEM #18 ON |
| | PREVIOUS REVIEW. |
| | |
| | 7) SPECIFY THE SIZE, NUMBER AND SPACING OF THE VERTICAL |
| | REINFORCEMENT OF THE CONCRETE BLOCK WALLS AT THE FIRST |
| | AND SECOND FLOORS AND THE MASONRY CHIMNEY. FBC* 106.1.2 |
| | SEE ITEM #22 ON PREVIOUS REVIEW. |
| | |
| | 8) SPECIFY THE CONNECTORS AND HANGERS FOR THE WOOD |
| | GIRDER TRUSSES AT THE SECOND FLOOR BALCONY. FBC* |
| | 106.1.2 |
| | |
| | 9) SHEET A.0 SPECIFIES R-19 ICYNENE INSULATION AND THE |
| | ENERGY CALCULATIONS SPECIFY R-30. PLEASE CORRECT. SEE |
| | #32 FROM PREVIOUS REVIEW. |
| | |
| | 10) THE PLANS SPECIFY ISONYNE (ICYNENE) ATTIC |
| | INSULATION THE MANUFACTURER'S SPECIFICATIONS THAT WERE |
| | SUBMITTED ARE FOR ANOTHER SPRAY FOAM INSULATION. PLEASE |
| | REVISE SHEET A.0. RATHER THAN SPECIFY A PARTICULAR |
| | BRAND, JUST SPECIFY SPRAY FOAM INSULATION. |
| | |
| | 11) THE SPRAY FOAM ATTIC INSULATION IS REQUIRED TO BE |
| | BE PROTECTED BY AN IGNITION BARRIER IN COMPLIANCE WITH |
| | R314.5.3 ATTICS. |
| | WHERE ATTIC ACCESS IS REQUIRED BY SECTION R807.1 AND |
| | WHERE ENTRY IS MADE ONLY FOR SERVICE OF UTILITIES, FOAM |
| | PLASTICS SHALL BE PROTECTED AGAINST IGNITION BY |
| | 1.5-INCH-THICK (38 MM) MINERAL FIBER INSULATION, 1 / 4 |
| | -INCH-THICK (6.4 MM) WOOD STRUCTURAL PANELS, 3 / 8 |
| | -INCH (9.5 MM) PARTICLEBOARD, 1/4-INCH (6.4 MM) |
| | HARDBOARD, 3 / 8 -INCH (9.5 MM) GYPSUM BOARD, OR |
| | CORROSION-RESISTANT STEEL HAVING A BASE METAL THICKNESS |
| | OF 0.016 INCH (0.406 MM) AND THE THERMAL BARRIER |
| | SPECIFIED IN SECTION R314.4 IS NOT REQUIRED. THE |
| | IGNITION BARRIER IS NOT REQUIRED WHERE THE FOAM PLASTIC |
| | INSULATION HAS BEEN TESTED IN ACCORDANCE WITH SECTION |
| | R314.6 . |
| | THE IGNITION BARRIER IS NOT REQUIRED WHEN THE FOAM HAS |
| | BEEN TESTED IN ACCORDANCE WITH R314.6 SPECIFIC |
| | APPROVAL. |
| | PLASTIC FOAM NOT MEETING THE REQUIREMENTS OF SECTIONS |
| | R314.3 THROUGH R314.5 SHALL BE SPECIFICALLY APPROVED ON |
| | THE BASIS OF ONE OF THE FOLLOWING APPROVED TESTS: |
| | FM4880, UL 1040, NFPA 286, OR UL 1715, OR FIRE TESTS |
| | RELATED TO ACTUAL END-USE CONFIGURATIONS. THE SPECIFIC |
| | APPROVAL SHALL BE BASED ON THE ACTUAL END USE |
| | CONFIGURATION AND SHALL BE PERFORMED ON THE FINISHED |
| | FOAM PLASTIC ASSEMBLY IN THE MAXIMUM THICKNESS INTENDED |
| | FOR USE. ASSEMBLIES TESTED SHALL INCLUDED SEAMS, JOINTS |
| | AND OTHER TYPICAL DETAILS USED IN THE INSTALLATION OF |
| | THE ASSEMBLY AND SHALL BE TESTED IN THE MANNER INTENDED |
| | FOR USE. SPECIFY HOW THE FOAM WILL BE PROTECTED FROM |
| | IGNITION ON THE PLANS OR PROVIDE ACCEPTABLE EVIDENCE OF |
| | THE REQUIRED TESTING. |
| | |
| | 12) PLEASE REMOVE THE OLD OR EXPIRED PRODUCT APPROVALS |
| | FROM THE SUBMITTAL. ONLY SUBMIT PRODUCT APPROVALS THAT |
| | WILL BE USED. REMOVE ANY DUPLICATE PRODUCT APPROVALS. |
| | INDICATE WHICH PRODUCT APPROVALS ARE FOR WHICH |
| | OPENINGS. |
| | |
| | 13) THE COMPONENT AND CLADDING PRESSURES ON S.1 FOR A |
| | TWO STORY BUILDING ARE WORST CASE AND DO NOT ACCOUNT |
| | FOR OPENING SIZE OR GARAGE DOORS. BECAUSE SEE FBC TABLE |
| | R301.2(2) AND TABLE R301.2(4). BECAUSE THESE PRESSURES |
| | ARE SPECIFIED SOME OF THE PRODUCT APPROVALS MAY HAVE |
| | PRESSURES THAT ARE NOT ADEQUATE. THE OVERHEAD GARAGE |
| | DOORS FOR EXAMPLE. PLEASE SPECIFY THE REQUIRED |
| | COMPONENT AND CLADDING PRESSURES AT THE OPENINGS ON THE |
| | PLANS. |
| | |
| | 14) THE PRODUCT APPROVAL FOR THE THERMA-TRU FIBERGLASS |
| | DOOR REQUIRES HURRICANE PANELS FOR THE NON-IMPACT RATED |
| | SIDELITES. SUBMIT PRODUCT APPROVALS FOR THE STORM |
| | PANELS. |
| | |
| | 15) SUBMIT THE NEW NOA #06-0807.07 FOR THE PGT FD 101 |
| | FRENCH DOORS. SEE ITEM #42 FROM PREVIOUS REVIEW. |
| | |
| | 16) SUBMIT THE NEW NOA #05-1129.11 FOR THE PGT CASEMENT |
| | WINDOWS. SEE ITEM #43 FROM PREVIOUS REVIEW. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |
| | |