Plan Review Notes
Plan Review Notes For Permit 06120693
Permit Number 06120693
Review Stop P
Sequence Number 1
Notes
Date Text
2006-12-28 14:43:13DENIED;
 1.SANITARY RISER DIAGRAM 2ND FLOOR SOUTH; MISSING
 AUTOMATIC CLOTHES WASHER AND ONE LAVATORY. THE BRANCH
 DRAIN FOR W/M IS REQUIRED TO BE 3" FBC-2004 PLUMBING
 SECTION406.3. THE WET VENT FOR THE MISSING LAV TO BE
 BETWEEN THE W/C AND THE SHOWER. THE W/M MUST DUMP DOWN
 STREAM OF THE BATHROOM GROUPS SECTION 909.1.
 2. THE SHOWERDRAIN MUST BE WITHIN 6' OF THE BREAK TO
 THE VENT SEE TABLE 906.1.
 3. ONE SET OF PLANS NOT SIGNED OR SEALED.
 ONE PAGE P-2 MARKED IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695