Plan Review Notes
Plan Review Notes For Permit 06120693
Permit Number 06120693
Review Stop M
Sequence Number 1
Notes
Date Text
2007-01-02 08:19:11*** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR A 19 AND A 17.30
 SEER A/C SYSTEM, MECHANICAL PLANS ARE CALLING FOR TWO
 13 SEER A/C SYSTEMS, THE TWO MUST COINCIDE, PLEASE
 CORRECT.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 3) ENERGY CALCULATIONS NEED THE JURISDICTION NUMBER ON
 THEM.
  
 4) MANUAL J CALCULATION DO NOT SHOW THE BUILDINGS
 NEEDED SENSIBLE BTU'S ON THEM, YOU MAY NEED THE LONG
 FORM TO GET THIS, PLEASE CORRECT.
  
 5) SEE PLANS PAGE M.1 SUPPLY AIR DUCT TO THE BATHROOM
 IN THE DEN NEEDS TO BE SIZED.
  
 6) SEE PLANS PAGE M.2 SUPPLY AIR DUCT TO BEDROOM #4
 NEEDS TO BE SIZED.
  
 7) SEE MECHANICAL PLANS A/C EQUIPMENT LISTING, AIR
 HANDLER #2 MODEL NUMBER, ARI DIRECTORY DOES NOT LIST
 THIS AIR HANDLER WITH THAT CONDENSER UNIT, PLEASE
 CORRECT.
  
 8) IF ANY APPLIANCES ARE GAS PLEASE NOTE SO ON
 MECHANICAL PLANS.
  
 9) THE ARCHITECT DID NOT SEAL ALL PAGES OF THE PLANS,
 PLEASE CORRECT PER FAC 61G1-16.003.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.