| Plan Review Notes For Permit 06120693 |
| Permit Number |
06120693 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-02 08:19:11 | *** DENIED *** | | | 1) ENERGY CALCULATIONS ARE CALLING FOR A 19 AND A 17.30 | | | SEER A/C SYSTEM, MECHANICAL PLANS ARE CALLING FOR TWO | | | 13 SEER A/C SYSTEMS, THE TWO MUST COINCIDE, PLEASE | | | CORRECT. | | | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 3) ENERGY CALCULATIONS NEED THE JURISDICTION NUMBER ON | | | THEM. | | | | | | 4) MANUAL J CALCULATION DO NOT SHOW THE BUILDINGS | | | NEEDED SENSIBLE BTU'S ON THEM, YOU MAY NEED THE LONG | | | FORM TO GET THIS, PLEASE CORRECT. | | | | | | 5) SEE PLANS PAGE M.1 SUPPLY AIR DUCT TO THE BATHROOM | | | IN THE DEN NEEDS TO BE SIZED. | | | | | | 6) SEE PLANS PAGE M.2 SUPPLY AIR DUCT TO BEDROOM #4 | | | NEEDS TO BE SIZED. | | | | | | 7) SEE MECHANICAL PLANS A/C EQUIPMENT LISTING, AIR | | | HANDLER #2 MODEL NUMBER, ARI DIRECTORY DOES NOT LIST | | | THIS AIR HANDLER WITH THAT CONDENSER UNIT, PLEASE | | | CORRECT. | | | | | | 8) IF ANY APPLIANCES ARE GAS PLEASE NOTE SO ON | | | MECHANICAL PLANS. | | | | | | 9) THE ARCHITECT DID NOT SEAL ALL PAGES OF THE PLANS, | | | PLEASE CORRECT PER FAC 61G1-16.003. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|