| 2006-12-28 08:46:03 | |
| | ** UNSAT ** |
| | |
| | |
| | ** PLEASE KNOW ANY REFERENCES TO THE FBC CHAPTER 1 IN |
| | THE FOLLOWING NOTES THE ADMINISTRATIVE SECTION AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH. |
| | |
| | 1) NOTE: PLEASE SEE ONLY ONE SET OF PLANS ARE SIGNED, |
| | DATED AND SEALED BY THE ARCHITECT OF RECORD. PLEASE BE |
| | SURE BOTH SETS ARE SIGNED AND SEALED. |
| | FS 481.221 |
| | |
| | 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED |
| | ON PLANS AS THIS PERMIT APPLICATION HAS BEEN MADE UNDER |
| | THE NEW 2005 NEC. |
| | THE FOLLOWING SHALL BE ON PLANS AT A MINIMUM ON |
| | ELECTRICAL SHEETS. |
| | 2005 NFPA-2005 |
| | 2002 NFPA-72 |
| | PLANS MAY NOT REFERENCE LATEST EDITION AS THE STATE OF |
| | FLORIDA ONLY JUST ADOPTED THE NEW REVISIONS TO THE 2004 |
| | FBC AND THE 2005 NEC. |
| | |
| | 3) NOTE: PLEASE SEENFPA-72 11-5.1.1, 11.8.3. PLEASE |
| | SEE NFPA-72 DEFINITIONS AS PLANS CALL FOR SD FOR SMOKE |
| | DETECTORS THIS IS OK, HOWEVER PLEASE KNOW IF THESE ARE |
| | INDEED SMOKE DETECTORS AS DEFINED IN NFPA72, THESE |
| | WOULD BE DEVICES WHICH ONLY DETECT AND WOULD SIGNAL TO |
| | OTHER ALARM/HORN DEVICES. NO ALARM HORN DEVICES ARE |
| | SHOWN. PLEASE INDICATE IF PART OF A FUTURE LV FA |
| | SYSTEM. |
| | PLEASE KNOW AS PER SECTIONS GIVEN IF THESE ARE INDEED |
| | DEVICES WHICH DETECT AND ALSO SOUND AN ALARM, THEN THEY |
| | WOULD BE LABELED AS SA FOR SMOKE ALARMS. |
| | PLEASE KNOW AS OF OCT 06 IT CAME TO OUR ATTENTION AT |
| | THE SOUTHERN SECTION MEETING FROM NFPA THAT IF UNITS |
| | ARE INDEED DEVICES WHICH DETECT AND SOUND AN ALARM, |
| | PLANS SHOULD SHOW THEM AS SA AND THIS IS NOT NEW IN THE |
| | CODE. THIS HAS BEEN AN ACCEPTED METHOD IN THE PAST TO |
| | SHOW SD FOR BOTH HOWEVER ALL PLANS SINCE OCT 06 SHOULD |
| | BE CHANGING IF WHERE APPLICABLE. |
| | PLEASE SEE MISSING SA/SD AT THE BOTTOM OF THE STAIRS |
| | LEADING TO THE FLOOR ABOVE AND MISSING ONE INSIDE AND |
| | OUTSIDE DEN AS THIS IS CONSIDERED AN ADAPTABLE SLEEPING |
| | ROOM. |
| | ANY DEVICES LOCATED O WITHIN 20FT OF COOKING APPLIANCES |
| | SHALL BE PHOTO-ELECTRIC OR RESETTING TYPE.11.8.3 PLEASE |
| | ADJUST PLANS AND NOTES. |
| | |
| | 4) NOTE: PLEASE SEE FBC 2004 13-103.1.1.1 WHICH |
| | REQUIRES THE TYPE OF RECESSED LIGHTS TO BE INSTALLED. |
| | PLEASE NOTE ON PLANS ACCORDINGLY. |
| | |
| | 5) NOTE: PLEASE CLARIFY RISER AS THIS SHOW 350MCM BEING |
| | INSTALLED TO FPL YET THE RISER ONLY INDICATES A 200A |
| | SERVICE BEING INSTALLED? |
| | FBC ADMIN SECTION 106.1.2 |
| | |
| | 6) NOTE: PLEASE ALSO VERIFY SERVICE AS SHOWN AND |
| | CORRELATE. PLEASE SEE RISER SHOWS THE PANEL H AS |
| | CONTAINING A MAIN BACK TO BACK WITH THE METER; HOWEVER |
| | PANEL SCHEDULE FOR H ONLY INDICATES THIS AS BEING A MLO |
| | PANEL. PLEASE SEE NOTE #8 AS AN EQUIPMENT GROUND IS |
| | SHOWN TO THE MAIN PANEL. |
| | IF THIS IS A METER/MAIN COMBO, PLEASE ADJUST PLANS AND |
| | RISER ACCORDINGLY. |
| | IF THIS IS INDEED THE CASE PLEASE SEE THE FOLLOWING |
| | TWO COMMENTS. |
| | PLEASE CLARIFY. 230.70, |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 7) NOTE: PLEASE PROVIDE THE NEW MAIN AIC RATING AS |
| | REQUIRED PER 110.9 |
| | FBC ADMIN SECTION 106.1.2, 106.3.5.4 |
| | |
| | 8) NOTE: PLEASE SEE IF A MAIN IS NOT LOCATED OUTSIDE |
| | THEN PLEASE SEE 250.6 AND 250.24B AS AN EQUIPMENT |
| | GROUNDING CONDUCTOR IS NOT INSTALLED FROM THE METER TO |
| | THE FIRST MEANS OF DISCONNECT. |
| | |
| | 9) NOTE: PLEASE SEE PANEL SCHEDULE AS SHOWN, PLEASE SEE |
| | KITCHEN GFI CIRCUITS SHOULD BE NOTED AS THE KITCHEN |
| | SMALL APPLIANCE CIRCUITS IF INDEED THESE WILL |
| | BE.(CLARIFICATION AS IT IS BEING ASSUMED THAT THESE |
| | ARE) |
| | 408.4 |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: PLEASE SEE THAT ALL ITEMS WHICH SEEM TO BE |
| | GAS APPLIANCES SHALL BE SHOWN ON PANEL SCHEDULE AS |
| | SUCH. WILL ELECTRICAL BE INSTALLED TO ANY OF THESE |
| | LOCATION FOR ANY OF THESE APPLIANCE TO BE ELECTRIC? IF |
| | SO, PLEASE ALSO INCLUDE ON PANEL SCHEDULE AND LOAD |
| | CALCULATIONS. |
| | PLEASE KNOW THAT THIS IS SOMETIMES DONE AND ONLY BEING |
| | NOTED FOR THE ELECTRICAL PART OF THIS COMMENT. PLEASE |
| | HOWEVER LIST AS GAS WHERE APPLICABLE. |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: PLEASE SEE THE CONDUCTORS SHOWN TO THE TWO |
| | A/C DISCONNECTS INDICATE THESE AS BEING THREE PHASE. |
| | PLEASE ADJUST SERVICE, CONDUCTORS, OR EXPLAIN THE 3RD |
| | CONDUCTOR AS SHOWN. |
| | FBC 106.1.2 |
| | |
| | 11) NOTE: PLEASE SEE DEN AREA WHICH SEEMS TO SHOW A |
| | RECEPT LOCATED IN THE FLOOR JUST ON THE OUTSIDE OF A |
| | WALL WHICH ALREADY CONTAINS A RECEPT. PLEASE SEE IF |
| | INDEED A FLOOR RECEPT PLEASE ADJUST NOTE AND SYMBOL FOR |
| | SUCH. |
| | FBC 106.1.2 |
| | |
| | 12) NOTE: PLEASE SEE 210.52 FOR SEVERAL MISSING |
| | REQUIRED RECEPTACLE FOR WALL SPACES 2FT OR MORE. PLEASE |
| | SEE ONE SET OF PLANS ARE REDLINED FOR MOST LOCATIONS. |
| | |
| | 13) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.52A FOR |
| | MISSING DINING AND OTHER SIMILAR AREAS AND CIRCUITING, |
| | LOADS AS REQUIRED. |
| | |
| | 14) NOTE:PLEASE CLARIFY IF THE LOAD ON THE POOL PUMP |
| | IS SHOWN AT THE CONTINUOUS DUTY AS ON LOAD CALCULATIONS |
| | OR PLEASE SHOW AT 125%. |
| | 215.3, 230.42 |
| | |
| | 15) NOTE: PLEASE SEE 210.70 AND LS 101 7.8, PLEASE SEE |
| | THE DEN SHALL BE REQUIRED TO CONTAIN A LIGHT FIXTURE OF |
| | SOME KIND BEFORE FINAL OR OTHER EXCEPTION FOR SWITCHED |
| | RECEPT ETC. |
| | PLEASE ADJUST PLANS AS NEEDED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |