Plan Review Notes
Plan Review Notes For Permit 06120693
Permit Number 06120693
Review Stop E
Sequence Number 1
Notes
Date Text
2006-12-28 08:46:03 
 ** UNSAT **
  
  
 ** PLEASE KNOW ANY REFERENCES TO THE FBC CHAPTER 1 IN
 THE FOLLOWING NOTES THE ADMINISTRATIVE SECTION AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE SEE ONLY ONE SET OF PLANS ARE SIGNED,
 DATED AND SEALED BY THE ARCHITECT OF RECORD. PLEASE BE
 SURE BOTH SETS ARE SIGNED AND SEALED.
 FS 481.221
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS AS THIS PERMIT APPLICATION HAS BEEN MADE UNDER
 THE NEW 2005 NEC.
 THE FOLLOWING SHALL BE ON PLANS AT A MINIMUM ON
 ELECTRICAL SHEETS.
 2005 NFPA-2005
 2002 NFPA-72
 PLANS MAY NOT REFERENCE LATEST EDITION AS THE STATE OF
 FLORIDA ONLY JUST ADOPTED THE NEW REVISIONS TO THE 2004
 FBC AND THE 2005 NEC.
  
 3) NOTE: PLEASE SEENFPA-72 11-5.1.1, 11.8.3. PLEASE
 SEE NFPA-72 DEFINITIONS AS PLANS CALL FOR SD FOR SMOKE
 DETECTORS THIS IS OK, HOWEVER PLEASE KNOW IF THESE ARE
 INDEED SMOKE DETECTORS AS DEFINED IN NFPA72, THESE
 WOULD BE DEVICES WHICH ONLY DETECT AND WOULD SIGNAL TO
 OTHER ALARM/HORN DEVICES. NO ALARM HORN DEVICES ARE
 SHOWN. PLEASE INDICATE IF PART OF A FUTURE LV FA
 SYSTEM.
 PLEASE KNOW AS PER SECTIONS GIVEN IF THESE ARE INDEED
 DEVICES WHICH DETECT AND ALSO SOUND AN ALARM, THEN THEY
 WOULD BE LABELED AS SA FOR SMOKE ALARMS.
 PLEASE KNOW AS OF OCT 06 IT CAME TO OUR ATTENTION AT
 THE SOUTHERN SECTION MEETING FROM NFPA THAT IF UNITS
 ARE INDEED DEVICES WHICH DETECT AND SOUND AN ALARM,
 PLANS SHOULD SHOW THEM AS SA AND THIS IS NOT NEW IN THE
 CODE. THIS HAS BEEN AN ACCEPTED METHOD IN THE PAST TO
 SHOW SD FOR BOTH HOWEVER ALL PLANS SINCE OCT 06 SHOULD
 BE CHANGING IF WHERE APPLICABLE.
 PLEASE SEE MISSING SA/SD AT THE BOTTOM OF THE STAIRS
 LEADING TO THE FLOOR ABOVE AND MISSING ONE INSIDE AND
 OUTSIDE DEN AS THIS IS CONSIDERED AN ADAPTABLE SLEEPING
 ROOM.
 ANY DEVICES LOCATED O WITHIN 20FT OF COOKING APPLIANCES
 SHALL BE PHOTO-ELECTRIC OR RESETTING TYPE.11.8.3 PLEASE
 ADJUST PLANS AND NOTES.
  
 4) NOTE: PLEASE SEE FBC 2004 13-103.1.1.1 WHICH
 REQUIRES THE TYPE OF RECESSED LIGHTS TO BE INSTALLED.
 PLEASE NOTE ON PLANS ACCORDINGLY.
  
 5) NOTE: PLEASE CLARIFY RISER AS THIS SHOW 350MCM BEING
 INSTALLED TO FPL YET THE RISER ONLY INDICATES A 200A
 SERVICE BEING INSTALLED?
 FBC ADMIN SECTION 106.1.2
  
 6) NOTE: PLEASE ALSO VERIFY SERVICE AS SHOWN AND
 CORRELATE. PLEASE SEE RISER SHOWS THE PANEL H AS
 CONTAINING A MAIN BACK TO BACK WITH THE METER; HOWEVER
 PANEL SCHEDULE FOR H ONLY INDICATES THIS AS BEING A MLO
 PANEL. PLEASE SEE NOTE #8 AS AN EQUIPMENT GROUND IS
 SHOWN TO THE MAIN PANEL.
 IF THIS IS A METER/MAIN COMBO, PLEASE ADJUST PLANS AND
 RISER ACCORDINGLY.
 IF THIS IS INDEED THE CASE PLEASE SEE THE FOLLOWING
 TWO COMMENTS.
 PLEASE CLARIFY. 230.70,
 FBC 106.1.2 ADMIN SECTION.
  
 7) NOTE: PLEASE PROVIDE THE NEW MAIN AIC RATING AS
 REQUIRED PER 110.9
 FBC ADMIN SECTION 106.1.2, 106.3.5.4
  
 8) NOTE: PLEASE SEE IF A MAIN IS NOT LOCATED OUTSIDE
 THEN PLEASE SEE 250.6 AND 250.24B AS AN EQUIPMENT
 GROUNDING CONDUCTOR IS NOT INSTALLED FROM THE METER TO
 THE FIRST MEANS OF DISCONNECT.
  
 9) NOTE: PLEASE SEE PANEL SCHEDULE AS SHOWN, PLEASE SEE
 KITCHEN GFI CIRCUITS SHOULD BE NOTED AS THE KITCHEN
 SMALL APPLIANCE CIRCUITS IF INDEED THESE WILL
 BE.(CLARIFICATION AS IT IS BEING ASSUMED THAT THESE
 ARE)
 408.4
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE THAT ALL ITEMS WHICH SEEM TO BE
 GAS APPLIANCES SHALL BE SHOWN ON PANEL SCHEDULE AS
 SUCH. WILL ELECTRICAL BE INSTALLED TO ANY OF THESE
 LOCATION FOR ANY OF THESE APPLIANCE TO BE ELECTRIC? IF
 SO, PLEASE ALSO INCLUDE ON PANEL SCHEDULE AND LOAD
 CALCULATIONS.
 PLEASE KNOW THAT THIS IS SOMETIMES DONE AND ONLY BEING
 NOTED FOR THE ELECTRICAL PART OF THIS COMMENT. PLEASE
 HOWEVER LIST AS GAS WHERE APPLICABLE.
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE THE CONDUCTORS SHOWN TO THE TWO
 A/C DISCONNECTS INDICATE THESE AS BEING THREE PHASE.
 PLEASE ADJUST SERVICE, CONDUCTORS, OR EXPLAIN THE 3RD
 CONDUCTOR AS SHOWN.
 FBC 106.1.2
  
 11) NOTE: PLEASE SEE DEN AREA WHICH SEEMS TO SHOW A
 RECEPT LOCATED IN THE FLOOR JUST ON THE OUTSIDE OF A
 WALL WHICH ALREADY CONTAINS A RECEPT. PLEASE SEE IF
 INDEED A FLOOR RECEPT PLEASE ADJUST NOTE AND SYMBOL FOR
 SUCH.
 FBC 106.1.2
  
 12) NOTE: PLEASE SEE 210.52 FOR SEVERAL MISSING
 REQUIRED RECEPTACLE FOR WALL SPACES 2FT OR MORE. PLEASE
 SEE ONE SET OF PLANS ARE REDLINED FOR MOST LOCATIONS.
  
 13) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.52A FOR
 MISSING DINING AND OTHER SIMILAR AREAS AND CIRCUITING,
 LOADS AS REQUIRED.
  
 14) NOTE:PLEASE CLARIFY IF THE LOAD ON THE POOL PUMP
 IS SHOWN AT THE CONTINUOUS DUTY AS ON LOAD CALCULATIONS
 OR PLEASE SHOW AT 125%.
 215.3, 230.42
  
 15) NOTE: PLEASE SEE 210.70 AND LS 101 7.8, PLEASE SEE
 THE DEN SHALL BE REQUIRED TO CONTAIN A LIGHT FIXTURE OF
 SOME KIND BEFORE FINAL OR OTHER EXCEPTION FOR SWITCHED
 RECEPT ETC.
 PLEASE ADJUST PLANS AS NEEDED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]