Plan Review Notes
Plan Review Notes For Permit 06120693
Permit Number 06120693
Review Stop B
Sequence Number 1
Notes
Date Text
2007-02-20 12:04:59DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) ON SHEET A.0 THERE IS A TYPO UNDER JURISDICTION.
 OALM SHOULD BE PALM.
  
 4) ON A.0 THE EXPOSURE CATEGORY SHOULD BE "B" NOT NEAR
 COASTAL.
  
 5) ON A.0 THE BUILDING CATEGORY IS II.
  
 6) THE ROOF DEAD LOAD ON A.O DOES NOT CONCUR WITH THE
 LOADS SPECIFIED ON S.1.
  
 7) SPECIFY THE ORIENTATION OF THE SITE PLAN ON A.0 AND
 SHOW THE LOCATION OF ALPINE RD.
  
 8) THE INSULATION NOTES ON A.0 DO NOT LIST THE EXTERIOR
 WOOD FRAME WALLS AT THE MASTER BEDROOM OR ADJACENT WOOD
 FRAME WALLS, FLOOR ABOVE COVERED PORCH AND FLOOR AT THE
 GARAGE.
  
 9) SHOW COMPLIANCE WITH FBC R302.1 EXTERIOR WALLS.
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL.
 EXCEPTION : DETACHED GARAGES ACCESSORY TO A DWELLING
 LOCATED WITHIN 2 FEET (610 MM) OF A LOT LINE SHALL BE
 PERMITTED TO HAVE ROOF EAVE PROJECTIONS NOT EXCEEDING 4
 INCHES (102 MM).
 PROJECTIONS EXTENDING INTO THE 6-FOOT (1829 MM)
 SEPARATION DISTANCE SHALL HAVE NOT LESS THAN 1-HOUR
 FIRE-RESISTIVE CONSTRUCTION ON THE UNDERSIDE. THE ABOVE
 PROVISIONS SHALL NOT APPLY TO WALLS WHICH ARE
 PERPENDICULAR TO A LINE EXTENDING FROM THE POINT FROM
 WHICH THE SEPARATION DISTANCE HAS BEEN MEASURED RUNNING
 AND PARALLEL TO THE PROPERTY LINE.
 EXCEPTION: TOOL AND STORAGE SHEDS, PLAYHOUSES AND
 SIMILAR STRUCTURES ARE NOT REQUIRED TO PROVIDE WALL
 PROTECTION BASED ON LOCATION ON THE LOT.
 THE DISTANCE TOO THE PROPERTY LINE IS 5'. SUBMIT A SITE
 PLAN SHOWING THE SEPARATION DISTANCE TO STRUCTURES ON
 THE ADJACENT PROPERTY WHERE DISTANCE TO PROPERTY LINE
 IS LESS THAN 6'.
  
 10)THE STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE. THE
 FIRST FLOOR ELEVATION IS REQUIRED TO BE A MINIMUM OF
 7'-6". AN ELEVATION CERTIFICATE WILL BE REQUIRED PRIOR
 TO C.O.
  
 11) R401.4 SOIL TESTS.
 IN AREAS LIKELY TO HAVE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER UNKNOWN SOIL CHARACTERISTICS, THE
 BUILDING OFFICIAL SHALL DETERMINE WHETHER TO REQUIRE A
 SOIL TEST TO DETERMINE THE SOIL?S CHARACTERISTICS AT A
 PARTICULAR LOCATION. THIS TEST SHALL BE MADE BY AN
 APPROVED AGENCY USING AN APPROVED METHOD.
 SUBMIT A GEOTECHNICAL REPORT TO VERIFY THE SAFE BEARING
 CAPACITY OF THE SOIL.
  
 12) SUBMIT A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048
 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
  
 13) SHOW COMPLIANCE WITH R322.1.1
 ALL NEW SINGLE-FAMILY HOUSES, DUPLEXES, TRIPLEXES,
 CONDOMINIUMS AND TOWNHOUSES SHALL PROVIDE AT LEAST ONE
 BATHROOM, LOCATED WITH MAXIMUM POSSIBLE PRIVACY, WHERE
 BATHROOMS ARE PROVIDED ON HABITABLE GRADE LEVELS, WITH
 A DOOR THAT HAS A 29-INCH (737 MM) CLEAR OPENING.
 HOWEVER, IF ONLY A TOILET ROOM IS PROVIDED AT GRADE
 LEVEL, SUCH TOILET ROOMS SHALL HAVE A CLEAR OPENING OF
 NOT LESS THAN 29 INCHES (737 MM).
  
 14) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS .
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER.
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3
 FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 15) SHOW COMPLIANCE WITH R309.2 SEPARATION REQUIRED.
 THE GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND
 ITS ATTIC AREA BY NOT LESS THAN 1/2 -INCH (12.7 MM)
 GYPSUM BOARD APPLIED TO THE GARAGE SIDE. GARAGES
 BENEATH HABITABLE ROOMS SHALL BE SEPARATED FROM ALL
 HABITABLE ROOMS ABOVE BY NOT LESS THAN 5 / 8 -INCH
 (15.9 MM) TYPE X GYPSUM BOARD OR EQUIVALENT. WHERE THE
 SEPARATION IS A FLOOR-CEILING ASSEMBLY, THE STRUCTURE
 SUPPORTING THE SEPARATION SHALL ALSO BE PROTECTED BY
 NOT LESS THAN 1/2 -INCH (12.7 MM) GYPSUM BOARD OR
 EQUIVALENT.
  
 16)SPECIFY THE WINDOW TYPES ON THE PLANS ( SHINGLE
 HUNG, ETC.).
  
 17)THE WINDOW IN BEDROOM #4 IS REQUIRED TO COMPLY
 WITH R310.1. EMERGENCY ESCAPE AND RESCUE REQUIRED.
  
 18)SHOW COMPLIANCE WITH R502.1.2 DRAFTSTOPPING
 REQUIRED.
 WHEN THERE IS USABLE SPACE ABOVE AND BELOW THE
 CONCEALED SPACE OF A FLOOR/CEILING ASSEMBLY, DRAFTSTOPS
 SHALL BE INSTALLED SO THAT THE AREA OF THE CONCEALED
 SPACE DOES NOT EXCEED 1,000 SQUARE FEET. DRAFTSTOPPING
 SHALL DIVIDE THE CONCEALED SPACE INTO APPROXIMATELY
 EQUAL AREAS.
  
 19) ON S.1 UPDATE THE MASONRY STANDARDS SPECIFIED TO
 THE 2002 EDITIONS AS LISTED IN THE REFERENCED STANDARDS
 IN CHAPTER 35 OF THE 2004 FBC.
  
 20) SPECIFY THE DIMENSIONS ON THE FOUNDATION PLAN ON
 S.2.
  
 21) SPECIFY THE FASTENER TYPES FOR THE WINDOW/DOOR BUCK
 ATTACHMENT DETAILS ON S.3.
  
 22) PROVIDE A COLUMN SCHEDULE ON THE STRUCTURAL PAGES
 WHICH SPECIFIES REINFORCEMENT.
  
 23) PROVIDE A STRUCTURAL DETAIL FOR THE ARCHED
 OPENINGS.
  
 24) SPECIFY ALL OF THE CONNECTORS FOR THE PORCH ROOF ON
 DETAIL 5/A.5. SEE MARKINGS ON PLANS.
  
 25) DETAIL 5/A5 SPECIFIES A TILE ROOF AND THE
 ELEVATIONS SHOW METAL ROOFS. PLEASE CLARIFY.
  
 26)UPLIFT CONNECTORS ARE REQUIRED FOR THE TRUSSES AT
 THE COVERED PORCH. PLEASE SPECIFY.
  
 27)THE 2ND FLOOR FRAMING PLAN ON S.3 SPECIFIES A
 DOUBLE LEDGER AT THE OUTER WALL OF THE COVERED PORCH
 AND SECTION 2/A.5 SHOWS THE TRUSSES ON TOP OF THE WALL.
 PLEASE CLARIFY.
  
 28) PROVIDE A DETAIL OF THE BAY WINDOW ROOF WITH
 CONNECTORS SPECIFIED. SPECIFY THE FRAMING AT WINDOWS,
 HEADERS, STRAPPING, ETC.
  
 29) PROVIDE DETAILS FOR THE BEAMS AND LINTELS INCLUDING
 REINFORCEMENT AT THE FIREPLACE. SEE SECTION 2/A.2.
  
 30)SPECIFY THE CONNECTORS AT THE SECOND FLOOR JOISTS
 THAT WILL BE USED TO RESIST LATERAL FORCES AT THE FLOOR
 DIAPHRAM.
  
 31)PROVIDE A DETAIL OF THE EXTERIOR WOOD FRAME LOAD
 BEARING WALL AT THE SECOND FLOOR MASTER BEDROOM.
  
 32) SHEET A.0 SPECIFIES R-19 ICYNENE INSULATION AND THE
 ENERGY CALCULATIONS LIST R-30. PLEASE CORRECT.
  
 33) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY CALC. FORM. SEE FBC CHAPTER 13.
  
 34) ICYNENE IS TYPICALLY USED IN UNVENTED ATTICS. THE
 SECTION ON A.2 SOWS THE INSULATION AT THE CEILING
 RATHER THAN AT THE ROOF, WHICH WILL REQUIRE ROOF
 VENTILATION PER R806.1.PLEASE CLARIFY.
  
 35) SUBMIT MANUFACTURER'S SPECS. AND INSTALLATION
 INSTRUCTIONS FOR THE ICYNENE INSULATION.
  
 36) SUBMIT MANUFACTURER'S SPECS. AND INSTALLATION
 INSTRUCTIONS FOR THE ISOKERN FIREPLACES AND FLUE
 ASSEMBLIES.
  
 37) SUBMIT TRUSS DRAWINGS AND LAYOUTS THAT HAVE BEEN
 SIGNED AND SEALED BY THE TRUSS ENGINEER AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD OF THE STRUCTURE.
  
 38) SUBMIT SHOP DRAWINGS FOR THE BALCONY GUARD RAILS
 FOR APPROVAL PRIOR TO INSTALLATION.
  
 39)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 40) SUBMIT PRODUCT APPROVALS FOR THE FOLLOWING:
 - METAL ROOF
  
 41) THE PRODUCT APPROVAL NOA FOR THE THERMA-TRU
 FIBERGLASS DOOR IS EXPIRED. SUBMIT CURRENT PRODUCT
 APPROVAL.
  
 42) THE NOA FOR THE PGT FD101 FRENCH DOORS HAS BEEN
 REVISED BY NOA #06-0807.07. SUBMIT NEW NOA.
  
 43) THE NOA FOR THE PGT CASEMENT WINDOWS HAS BEEN
 REVISED BY NOA # 05-1129.11. SUBMIT NEW NOA. PLEASE
 SPECIFY THE APPROPRIATE WINDOW INFORMATION SUCH AS
 SIZE, GLASS TYPE AND DESIGN PRESSURE BY CIRCLING THEM
 ON THE TABLES IN THE NOA.
  
 45) THE NOA FOR THE PGT 2" MULLINS IS EXPIRED. SUBMIT
 CURRENT NOA.
  
 46) SPECIFY WHICH WINDOWS WILL BE MULLED TOGETHER.
  
 47) SPECIFY WHICH ATTACHMENT METHOD WILL BE USED TO
 INSTALL THE CONCRETE ROOF TILE. CIRCLE THE APPROPRIATE
 ITEM IN THE PRODUCT APPROVAL.
  
 48) THE INSTALLATION DRAWING FOR THE GARAGE DOOR IS
 ONLY PARTIALLY LEGIBLE. SUBMIT CLEAR COPIES. THE DESIGN
 PRESSURES OF -40 PSF IS TOO LOW BASED ON THE REQUIRED
 PRESSURES THAT ARE SPECIFIED ON S1.
  
 IN ORDER TO EXPEDITE PLAN REVIEW, PLEASE INSERT THE NEW
 SHEETS INTO THE PLANS MAKING TWO COMPLETE SETS AND
 SUBMIT ONE SET OF THE OLD PLAN SHEETS FOR REFERENCE
 PURPOSES. A RESPONSE LETTER STATING HOW THE COMMENTS
 HAVE BEEN ADDRESSED WILL ALSO BE HELPFUL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  
  
  
  
  
  
  