Plan Review Notes
Plan Review Notes For Permit 06120690
Permit Number 06120690
Review Stop B
Sequence Number 1
Notes
Date Text
2006-12-27 12:44:27BUILDING PLAN REVIEW
 PERMIT:06120690
 ADD:219 BAKER DR.
 CONT:BAKER SOUTH ROOFING
 TEL: (561)752-8886
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)THE PRODUCT APPROVAL FOR THE FLAT ROOF REQUIRES
 CALCULATIONS PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINGEER, ARCHITECT, OR ROOF
 CONSULTANT. SEE GENERAL LIMITATION #7ON PAGE #44. DUE
 TO THE FACT THAT THEROOF PRESSURES ARE LOWER THAN THE
 PRESSURES IN TABLE 1609.6.2.1(2), CALCULATIONS WILL BE
 REQUIRED ACCORDING TO THE PRODUCT APPROVAL GENERAL
 LIMITATION #7. YOU MAY CHOOSE A DIFFERENT PRODUCT WHICH
 HAS HIGHER PRESSURES OR PROVIDE THE CALCULATIONS.
  
 2)ON THE APPLICATION, INDICATE THAT A FLAT ROOF WILL
 ALSO BE RE-ROOF AND STATE THE SQUARE FOOTAGE OF THE
 FLAT ROOF AREA.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726