| Plan Review Notes For Permit 06120663 |
| Permit Number |
06120663 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-16 12:24:21 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 2) SEE PAGE M101 EF-1, SEE HIGH LIGHTED 4_ M701 AND | | | HIGH LIGHTED EXISTING O/A, PLEASE REMOVE THESE | | | NOTATIONS AS THIS IS AN EXHAUST FAN. | | | | | | 3) SEE PAGE M101, ALL RETURN AIR GRILLS NOTEDAA/-, | | | CAN NOT DETERMINE SIZE, PLEASE CORRECT. | | | | | | 4) SEE PAGE M801 EQUIPMENT SCHEDULE, CONDENSER UNIT, | | | RATING EER, DO YOU MEAN SEER, IF SO PLEASE CORRECT. | | | | | | 5) SHOW MODEL NUMBERS FOR ALL AHU'S AND CONDENSER UNITS | | | IN EQUIPMENT SCHEDULE. | | | | | | 6) A FIRE DAMPER IS REQUIRED AT 8" SUPPLY DUCT | | | PENETRATING FIRE RATED WALL IN CORRIDOR, PER 2004 FBC/M | | | 607.5.2. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|