| 2007-01-14 18:04:29 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE THE PLANS SHALL STATE THE INTENDED |
| | OCCUPANCY AND TENANT MATERIALS. |
| | PLEASE SEE THE DELIVERY AREA STATES A CHAINS LINK FENCE |
| | FOR WHAT SEEMS LIKE IT SHOULD BE A TENANT SEPARATION? |
| | PLEASE KNOW THIS INFORMATION IN QUESTION HAS BEEN |
| | FORWARDED TO THE PLAN REVIEW STAFF WHICH WAS PART OF |
| | THE PREVIOUS PROJECT FOR THE ADJACENT BUILD OUT. |
| | TENANT SEPARATION? |
| | PLEASE KNOW THAT DUE TO THIS INFORMATION NOT STATED ON |
| | PLANS, SOME ITEMS FOR CODE COMPLIANCE REVIEW CAN NOT BE |
| | DONE AT THIS TIME. |
| | NEC 500. |
| | |
| | 2) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON |
| | PLANS FOR THE DESIGNS WHICH THEY ARE UNDER. |
| | PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER |
| | DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE |
| | RELEVANT. |
| | 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70 |
| | (NEC). |
| | PLEASE SEE THE OTHER CODES WHICH ARE STATED ON PLANS |
| | FOR ELECTRICAL SHEETS WHICH ARE ALREADY STATED ARE: |
| | 2002 NFPA-72 AND 2003 NFPA-101. |
| | |
| | 3) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS PER |
| | 13-415.1.AB.1, PERFORMANCE CALCULATIONS PER 13-415.2. |
| | THESE ARE REQUIRED TO BE SIGNED DATED AND SEALED BY THE |
| | DESIGNER OF RECORD. |
| | PLEASE SUBMIT A FIXTURE LEGEND FOR LIGHTING FIXTURES |
| | TO BE INSTALLED AND CORRELATE WITH THE IDENTIFICATION |
| | ON PLANS. PLEASE BE SURE TO CORRELATE WITH THE |
| | PERFORMANCE CALCULATIONS AND ENERGY CALCULATIONS. |
| | PLEASE SEE THE METHOD B SUBMITTED DOES NOT INDICATE |
| | AUTOMATED CONTROLS ETC. |
| | PLEASE SEE LIGHTING DENSITIES. |
| | PLEASE CLARIFY HOW FINE STORAGE IS DETERMINED. THIS |
| | SHALL BE REVIEWED BY THIS OFFICE FOR FINAL |
| | DETERMINATION FOR LIGHTING ALLOWANCE. |
| | PLEASE SEE 13-415.2.ABC.1.3 FOR EXTERIOR LIGHTING |
| | ALLOWANCE AND SHOW COMPLIANCE. |
| | NOT ENOUGH INFORMATION ON LIGHTING ALLOWANCES IS |
| | PROVIDED. |
| | |
| | 4) NOTE: PLEASE SEE THE 2006 REVISIONS TO THE 2004 FBC |
| | CHAPTER 13. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SUBMIT AUTOMATED LIGHTING CONTROL METHODS, |
| | SCHEDULING, DEVICES AND TYPES OF DEVICES. |
| | PLEASE INDICATE THE MAXIMUM TIMES ON ANY OVER RIDE |
| | DEVICES. (30 MINS FOR OCCUPANCY TYPE AND 4HRS MAX FOR |
| | TIMER TYPE. |
| | PLEASE PROVIDE A DETAIL FOR THE CIRCUITING THE |
| | EMERGENCY AND EXIT LIGHTS. (THERE IS A NOTE ON PLANS, |
| | HOWEVER SUBMIT DETAIL AS NUMEROUS SITUATIONS IN THE |
| | JURISDICTION HAS HAD THESE FIXTURES BEING WIRED ON THE |
| | LOAD SIDE OF THESE DEVICES. |
| | PLEASE KNOW AS NO INFORMATION WAS SUBMITTED FOR REVIEW, |
| | A COMPLETE REVIEW FOR COMPLIANCE CAN NOT BE DONE AT |
| | THIS TIME. |
| | |
| | 5) NOTE: PLEASE PROVIDE PHOTO-METRICS FOR THE EGRESS |
| | AREAS TO THE PUBLIC RIGHT OF WAY INCLUDING STAIRS. |
| | PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2 |
| | |
| | 6) NOTE: PLEASE COMPLETE SERVICE RISER DIAGRAM WITH THE |
| | FOLLOWING INFORMATION NOT SHOWN. |
| | PLEASE SEE MISSING CONDUCTORS FROM GUTTER TO METER AND |
| | TO MAIN. |
| | PLEASE SEE MISSING SIZE AND OVER CURRENT PROTECTION OF |
| | MAIN. |
| | PLEASE SE MISSING AIC RATING FOR NEW MAIN. (EVEN THOUGH |
| | NOTE IS ON 801 FOR OTHER EQUIPMENT). |
| | PLEASE INDICATE A "FOATING NEUTRAL"AT THE NEW METER. |
| | PLEASE REMOVE ALL REFERENCES TO "BUILDING #4"MAIN/ |
| | SERVICE AS THERE IS ONLY ONE SERVICE ON THIS BUILDING. |
| | PLEASE SEE NOTES ON RISER. |
| | PLEASE PROVIDE THE COMPLETE RISER AND LOADS ON THE |
| | EXISTING RISER WITH NEW LOADS BEING ADDED. |
| | |
| | 215.5, 215.3, 220.12, 220.14, 220.42, 220.42 ETC |
| | 110.9, 250.6, 250.24B, ETC |
| | FBC 106.1.2 , 106.3.5.1.2 ADMIN SECTION. |
| | |
| | 7) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR HORN, |
| | STROBES AND/OR HORN STROBE DEVICES PER FBC 11-4.28.1, |
| | .2 AND .3(4). |
| | THE INSTALLATION OF ANY ADDITIONAL DEVICES TO THE |
| | EXISTING FIRE ALARM SYSTEM WILL BE REQUIRED UNDER |
| | SEPARATE PLANS, PERMIT, HOWEVER THESE REQUIRED LEVELS |
| | ARE TO BE SHOWN ON BASE PLANS. |
| | |
| | 8) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS EMERGENCY |
| | LIGHTS AND EXIT LIGHTS ON THEIR OWN CIRCUIT? |
| | PLEASE SEE 700.12E. |
| | |
| | 9) NOTE: PLEASE BE SURE TO INDICATE ALL CIRCUITS ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULE. |
| | 106.1.2, 106.3.5.1.2 |
| | NEC 408.4, 310.16, 240.4 FOR VERIFICATION. |
| | |
| | ** PLEASE KNOW AS THERE IS INFORMATION NOT SUBMITTED A |
| | ND CHANGES IN PLANS WILL BE REQUIRED, THERE MAY BE |
| | COMMENTS ON THE NEXT REVIEW DUE TO ANY POSSIBLE |
| | CHANGES. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |