| 2007-03-08 07:55:18 | *** UNSAT 3RD REVIEW *** |
| | |
| | 1) NOTE: PLEASE SEE THE FIRST REVIEW WHICH REQUESTED |
| | NEW CODES TO BE PLACED ON PLANS.THIS WAS DONE AND |
| | CORRECTED ON PREVIOUS REVIEW HOWEVER PLEASE SEE NEW |
| | ELECTRICAL NOTES NOW ADDED TO SHEET 2.0E CONTAINS THE |
| | WRONG CODES FOR THE NEC AND THE YEARS FOR THE LS 101 |
| | AND NFPA-72 ARE NOT SHOWN. |
| | PLEASE LIST AS STATED ON FIRST REVIEW NOTES |
| | 2005 NFPA-70 (NEC) |
| | 2003 NFPA-101( LIFE SAFETY CODE) |
| | 2002 NFPA-72 |
| | * THE CORRECT CODE FOR THE FBC 2004 W/ 2006 REVISIONS |
| | WAS ADDED. |
| | |
| | 2) NOTE: PLEASE SEE FIRST REVIEW NOTES WHICH MENTIONED |
| | THAT THE RISER SHOWS A PANEL *H* AND BOTH PANEL |
| | SCHEDULES SUBMITTED WERE A AND B. THIS WOULD HAVE BEEN |
| | REDLINED, HOWEVER AS PLANS ARE COMING BACK FOR OTHER |
| | CORRECTIONS PLEASE CORRECT AT THIS TIME. |
| | |
| | 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AND THE |
| | PLANS DO NOT CORRELATE. |
| | PLEASE SEE THE FIXTURE LEGEND WHICH THE 2X4 FLUORESCENT |
| | FIXTURES ARE SHOWING A #=# FOR THE LAMPS?? |
| | PLEASE SEE MANY OF THE FIXTURES INDICATE SOME SORT OF |
| | 1-L, 2-L, 3-L AND 4-L ON THEM, HOWEVER NOT ALL. |
| | PLEASE SEE OF THIS IS FOR THE NUMBER OF LAMPS IN EACH |
| | FIXTURE THIS DOES NOT CORRELATE WITH THE CALCULATIONS. |
| | PLEASE KNOW EVEN IF THIS IS NOT THE NUMBER OF LAMPS AND |
| | THE NUMBER OF LAMPS ON EACH IS DIVIDED BY THE TOTAL |
| | FIXTURE WATTAGE ON CALCULATIONS MAKING THESE ALL FOUR |
| | LAMPS FIXTURES AT 32W EACH, THIS WOULD STILL NOT |
| | CORRELATE WITH ALL FIXTURES ON PLANS AND ENERGY |
| | CALCULATIONS. |
| | PLEASE SEE MEN'S AND WOMEN'S BATHROOMS. HOW DOES EACH |
| | OF THESE SHOW 64 WATTS ON LOAD CALCULATIONS IF THESE |
| | FIXTURES ARE 4-LAMP? PLEASE SEE THE FIXTURE LEGEND DOES |
| | NOT LEND ANY INFORMATION ON TWO TYPES OF 2X4 FIXTURES? |
| | PLEASE SEE THE SCONE AS SHOWN ON PLANS COULD NOT FOUND |
| | FIGURED INTO CALCULATIONS. |
| | PLEASE SEE THE ONE BATHROOM SHOWS 2-2X2 FIXTURES AND AS |
| | FIXTURE LEGEND STATES THESE ARE 2-32W LAMPS IN EACH, |
| | YET THE CALCULATIONS ONLY SEEM TO INDICATE ONE FIXTURE |
| | AT 64W'S?? |
| | * PLEASE SEE THE ENERGY CALCULATIONS *INPUT DATA* FOR |
| | ELECTRICAL IS THE SAME SHEETS IN WHICH THIS REVIEWER |
| | HAD REDLINED AS THE SAME CIRCLES PREVIOUSLY PLACED ON |
| | THEM DURING REVIEW ARE NOW BACK ON SHEETS. |
| | |
| | 4) NOTE: NOTICE TO THE ENGINEER. IT IS THE |
| | RESPONSIBILITY OF THE ENGINEER OF RECORD TO REVIEW ALL |
| | PLANS AND DOCUMENTS UNDER HIS DIRECT SUPERVISION BEFORE |
| | SIGNING, DATING AND SEALING SAID PLANS OR DOCUMENTS. |
| | SEE FLORIDA STATUTES 471.025(2). |
| | PLEASE KNOW ONE SET OF ELECTRICAL PLANS AND ENERGY |
| | CALCULATIONS ARE BEING RETAINED AND PLACED WITH |
| | PREVIOUS RETAINED PLANS FOR POSSIBLE REVIEW FROM THE |
| | FLORIDA BOARD OF PROFESSIONAL ENGINEERS. |
| | PLEASE ALSO SEE THE EXACT TEXT EXTRACTED FROM PART |
| | (3). |
| | ************************************************ |
| | (3)NO LICENSEE SHALL AFFIX OR PERMIT TO BE AFFIXED |
| | HIS OR HER SEAL, NAME, OR DIGITAL SIGNATURE TO ANY |
| | PLAN, SPECIFICATION, DRAWING, FINAL BID DOCUMENT, OR |
| | OTHER DOCUMENT THAT DEPICTS WORK WHICH HE OR SHE IS NOT |
| | LICENSED TO PERFORM OR WHICH IS BEYOND HIS OR HER |
| | PROFESSION OR SPECIALTY THEREIN. * |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |