Plan Review Notes
Plan Review Notes For Permit 06120650
Permit Number 06120650
Review Stop P
Sequence Number 2
Notes
Date Text
2007-02-09 13:43:44DENIED 2ND TIME
 REFERENCE: FBC-2004 PLUMBING; FBC-2004 CHAPTER 1, CITY
 OF WEST PALM BEACH AMENDMENTS;
  
 PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION
 AND/OR CHANGES MADE TO PLANS.
  
 ****IMPORTANT****
 PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM THE
 PREVIOUS REVIEW WITH A(NO), (OK) OR (NO/OK).
  
 A) A (NO), WILL CONTAIN A FURTHER EXPLANATION AS TO
 WHY THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH
 THE PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW
 NOTE #1
  
 B) A (OK), WILL HAVE NO COMMENTS EXCEPT PERHAPS A
 REFERENCE TO SEE **NEW NOTES**. THE PREVIOUS REVIEW
 NOTE WILL BE REMOVED.
  
 C) A (NO/OK), WILL HAVE FURTHER EXPLANATION AS PART OF
 THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL.
 THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS
 REVIEW NOTE #1**
  
 D) NEW NOTES WILL BE ADDED TO THE END AND BE LABELED
 **NEW NOTES**
  
 1. (NO) SHEET 3.OP INDICATES GREASE TRAP HAS BEED
 WAIVED BY THE CITY OF WEST PALM BEACH WATER UTILITIES.
 NOTE: THERE IS NO WAIVER OF THE GREASE INTERCEPTOR
 PLEASE REFERENCE THE ATTACHED SHEET FROM EVIRONMENTAL
 COMPLIANCE INDICATING A RECOMMENDED INTERCEPTOR SIZE OF
 1250 GAL. PLEASE REVISE RESUBMITTED PRINTS TO REFLECT
 THE REQUIRED 1250 GAL. GREASE INTERCEPTOR. ANY
 QUESTIONS ABOUT THE ATTACHED ENVIRONMENTAL COMPLIANCE
 SHEET PLEASE CONTACT THE FOLLOWING. (UTILITIES REP.)
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE (561) 822-2272.
  
 2. (OK)
  
 3. SHEET 3.0P SANITARY RISER AND PLUMBING PLAN; SHEET
 1.1A EQUIPMENT SCHEDULE;
 A} (OK)
 B} (OK)
 C} (NO} GREASE SYSTEM MUST DRAIN DOWN STREAM OF THE
 WET VENTED BATHROOMS PER FBC-2004, SECTION 909.1. IT IS
 INDICATED CORRECT ON THE PLUMBING PLAN, BUT IS NOT
 BEING INDICATED ON THE SANITARY ISOMETRIC RISER
 DIAGRAM. PLEASE CORRELATE THE DRAWINGS ON THE
 RESUBMITTAL.
 D} (NO) DELETE SAMPLE POINT FROM RESUBMITTED DRAWINGS
 AND ADD REQUIRED 1250 GAL. GREASE INTERCEPTOR.REFERENCE
 COMMENT #1.
 E} (OK)
 F} (OK)
  
 4. PER FBC-2004 CHAPTER 1 SECTION 106.3.5.1.3 THE
 FOLLOWING INFORMATION IS REQUIRED FOR THE POTABLE WATER
 SYSTEM:
 A} (NO/OK) REFERENCE NEW COMMENTS BELOW.
 B} (OK)
 C} (OK)
  
 **NEW COMMENT**
 5. SHEET 3.0P WATER RISER: PER FBC-2004 PLUMBING,
 SECTION 606.1(7) LOCATION OF FULL-OPEN VALVE REQUIRED
 ON SUPPLY PIPE TO EVERY WATER HEATER. PLEASE INDICATE
 VALVE ON THE RESUBMITTAL.
  
 6. SHEET 3.0P WATER RISER: PER FBC-2004 PLUMBING,
 SECTION 604.9 A WATER-HAMMER ARRESTOR SHALL BE
 INSTALLED WHERE QUICK CLOSING VALVES UTILIZED. PLEASE
 ADD THIS TO SHEET 3.0P WATER RISER AND CLEARLY INDICATE
 ALL WATER-HAMMER ARRESTORS. (NOTE; PRINT STATES "ADD
 WATER-HAMMER ARRESTOR @ EA. FIXTURE GROUP") THAT IS NOT
 WHAT THE CODE STATES, DOES EACH FIXTURE GROUP HAVE
 QUICK CLOSING VALVES? PLEASE CLARIFY ON THE
 RESUBMITTAL.
  
 7. SHEET 3.0P WATER RISER: PER FBC-2004 CHAPTER 1,
 CITY OF WEST PALM BEACH AMENDMENTS, SECTION 106.1
 INFORMATION ON CONSTRUCTION DOCUMENTS: CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND OF THE EXTENT OF THE WORK
 PROPOSED. PLEASE CLEARLY IDENTIFY ALL FIXTURES ON THE
 RESUBMITTED WATER RISER.
  
 8. PLEASE REFERENCE ELECTRICAL COMMENT #17.
  
 **********IMPORTANT INFORMATION
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  