| Date |
Text |
| 2007-02-09 15:13:09 | DENIED 2ND TIME |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW |
| | WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW |
| | COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION |
| | AND/OR CHANGES MADE TO PLANS. |
| | |
| | ****IMPORTANT**** PLEASE SEE THE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM THR PREVIOUS REVIEW WITH A (NO). (OK) OR |
| | (NO/OK). |
| | |
| | A) A (NO), WILL CONTAIN A FURTHER EXPLANATION AS TO |
| | WHY THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH |
| | THE PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW |
| | NOTE #1. |
| | |
| | B) A (OK), WILL HAVE NO COMMENTS EXCEPT PERHAPS A |
| | REFERENCE TO SEE **NEW NOTES** THE PREVIOUS REVIEW NOTE |
| | WILL BE REMOVED. |
| | |
| | C) A (NO/OK), WILL HAVE FURTHER EXPLANATION AS PART OF |
| | THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL. |
| | THE PREVIOUS REVIEW WILL BE NOTED **PREVIOUS REVIEW |
| | NOTE#1** |
| | |
| | D) NEW NOTES WILL BE ADDED TO THE END AND BE LABELED |
| | **NEW NOTES** |
| | |
| | 1. (NO)SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE CORRESPONDING |
| | LENGTHS INDICATED ON SHEET 3.0P GAS RISER. PLEASE |
| | CORRECT AND RESUBMIT. |
| | |
| | 2. (OK) |
| | |
| | 3. (NO)SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: NOW THAT THE GAS TYPE IS INDICATED AS LP, PLEASE |
| | INDICATE ON THE RESUBMITTED DRAWINGS THE TANK LOCATION, |
| | LOCATION OF 1ST AND 2ND STAGE REGULATORS AND ALL |
| | RELATED PIPING WITH CUT LENGTHS AND SIZES. |
| | |
| | 4. (NO)SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | NOTE:PLEASE SUBMIT MANUFACTURER SPECIFICATION SHEETS |
| | FOR THE GAS APPLIANCES TO VERIFY BTU LOADS, THE |
| | EMERGENCY SHUT OFF VALVE TO VERIFY COMPLIANCE AND THE |
| | 1ST AND 2ND STAGE REGULATORS TO VERIFY COMPLIANCE. |
| | |
| | **NEW COMMENT** |
| | |
| | 5. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | 6. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | **********IMPORTANT INFORMATION |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |
| | |