Plan Review Notes
Plan Review Notes For Permit 06120650
Permit Number 06120650
Review Stop E
Sequence Number 2
Notes
Date Text
2007-02-05 16:00:56******* UNSAT 2ND REVIEW ******
  
 *** PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION
 AND/OR CHANGES MADE TO PLANS.
  
 **** IMPORTANT****
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 THE PREVIOUS REVIEW WITH A *NO*, *OK* OR *NO/OK*.
  
 A) A, NO WILL CONTAIN A FURTHER EXPLANATION AS TO WHY
 THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH THE
 PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW NOTE
 #1**
  
 B) A, OK, WILL HAVE NO COMMENTS EXCEPT PERHAPS A
 REFERENCE TO SEE ** NEW NOTES*. THE PREVIOUS REVIEW
 NOTE WILL BE REMOVED.
  
 C) A, NO/OK, WILL HAVE FURTHER EXPLANATION AS PART OF
 THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL.
 THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS
 REVIEW NOTE #1**
  
 D) NEW NOTES WILL BE ADDED TO THE END AND LABELED **
 NEW NOTES **
  
  
  
 1) NOTE: OK.
  
 2) NOTE: NO.
 PLEASE SEE THERE WERE NO TIMES SUBMITTED.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO NOT
 CORRELATE WITH THE FIXTURES, WATTAGES, THE NUMBER OF
 FIXTURES, AND THE TYPE OF FIXTURES ETC WHICH ARE ON
 PLANS.
 PLEASE SEE THE CALCULATIONS SUBMITTED AND COORDINATE
 WITH PLANS.
  
 ** PREVIOUS REVIEW NOTE REVIEW#1**
 PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, .1.2 AND
 .1.3
 PLEASE INDICATE SCHEDULING, OVER RIDE DEVICES AT
 INGRESS/EGRESS, SEPARATE SPACES, TIMES ON ALL OVER RIDE
 DEVICES.
 PLEASE SEE 13-415.1.AB.1, 13-415.2, AND 13-415.2.ABC.1
 ENERGY CALCULATIONS ARE SUBMITTED HOWEVER THEY ARE NOT
 SIGNED, DATED OR SEALED BY THE ENGINEER OF RECORD.
 PLEASE CLARIFY PERFORMANCE CALCULATIONS AND HOW METHOD
 A CAN BE USED ON AN EXISTING SPACE OR IS THIS AN
 EXISTING SHELL WITH NEW EXTERIOR WALL BEING BUILD OUT
 FOR INTERIOR USE.
  
 3) NOTE: OK.
  
 4) NOTE: NO, PLEASE SEE COMMENTS FROM FIRE REVIEW WHERE
 COOKING WITH GREASE LADEN VAPORS WHICH WILL REQUIRE A
 HOOD OF SORTS, AND AS THIS APPEARS TO BE THE CASE,
 ELECTRICAL FOR HOOD NEEDS TO BE SHOWN. THERE IS NOTHING
 LOCATED ON PLANS FOR SUCH AND ANY SHUT OFF OF ANY
 ELECTRICAL UNDER HOOD (WHERE ELECTRIC IS INSTALLED).
 PLEASE SEE COMMENT #7 WITH RESPECT TO MISSING
 CIRCUITING ON PLANS.
  
 **PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE NFPA-96 AND CLARIFY ANY LIGHTING AND
 ELECTRICAL WHICH MAY BE PART OF ANY HOOD SYSTEM WHICH
 IS REQUIRED TO CONTAIN SHUNT TRIP DEVICES/BREAKERS.
  
 5) NOTE: NO? NO NOTES, RESPONSE OR NOTES COULD BE FOUND
 AND PANELS SCHEDULE DOES NOT SEEM TO INDICATE ANY
 ELECTRICAL FOR THIS, NEW OR EXISTING.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE CLARIFY NEW OR EXISTING ROOF TOP GFI FOR THE RTU
 A/C SYSTEM.
 210.63, 210.8
  
 6) NOTE: OK.
  
 7) NOTE: NO.
 PLEASE SEE THERE ARE SEVERAL ITEMS ON PLANS WHICH DO
 NOT CORRELATE WITH THE PANEL SCHEDULES.
 PLEASE SEE THERE ARE ITEMS ON PANEL SCHEDULES NOT ON
 PLANS.
 PLEASE SEE THERE ARE ELECTRICAL ITEMS ON PLANS (LIGHTS)
 WHICH DO NOT INDICATE ANY CIRCUITING.
 PLEASE SEE PANEL SCHEDULE WHICH DOES NOT INCLUDE ALL
 CIRCUITS ON PLANS.
 PLEASE SEE ITEMS ON PANEL SCHEDULE SHOWN AS 220V , YET
 ON 1-POLE BREAKERS.
 ETC.
 ONE SET OF PLANS HAS MANY OF THESE ITEMS REDLINED,
 HOWEVER NOT ALL.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE PROVIDE ALL CIRCUITING ON PLANS AND CORRELATE
 WITH THE SUBMITTED PANEL SCHEDULE(S). PLEASE SEE SOME
 MISSING FOR LIGHTING, RECEPTS ETC.
 FBC 106.1.2, 106.3.5.1.2, NEC 408.4, 310.16 ETC
  
 8) NOTE: NO, PLEASE SEE AS NOTE #7 ABOVE MENTIONS,
 PLEASE SEE FIXTURE(S) WHICH CIRCUITING IS MISSING.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE 700.12 FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTS.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE:
  
 13) NOTE: OK.
  
 14) NOTE: OK, VALUE INCREASED.
  
 15) NOTE: OK.
  
 16) NOTE: NO, SAME NOTE. PLEASE SEE THE FOLLOWING IS
 TEXT EXTRACTED FROM THE CODE TO HELP EXPLAIN THE
 PREVIOUS NOTE AS NO CHANGES WERE MADE TO THIS COMMENT.
 *SECTION 210.8(B)(2), WHICH WAS NEW FOR THE 2002 CODE,
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT RECEPTACLES IN
 NON-DWELLING-TYPE KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO ALL 15- AND 20-AMPERE, 125-VOLT
 KITCHEN RECEPTACLES, WHETHER OR NOT THE RECEPTACLE
 SERVES COUNTERTOP AREAS.*
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE 210.8B3 FOR GFP PROTECTION FOR ALL 15/20A
 120V RECEPTS IN KITCHEN/ KITCHEN AREAS.
  
  
 *** NEW NOTE **
  
 17) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTE GIVEN AT THIS TIME.
 ONE SET OF ELECTRICAL PLANS AND ENERGY CALCULATIONS ARE
 BEING RETAINED BY THIS OFFICE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]