| 2007-02-05 16:00:56 | ******* UNSAT 2ND REVIEW ****** |
| | |
| | *** PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW |
| | WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW |
| | COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION |
| | AND/OR CHANGES MADE TO PLANS. |
| | |
| | **** IMPORTANT**** |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | THE PREVIOUS REVIEW WITH A *NO*, *OK* OR *NO/OK*. |
| | |
| | A) A, NO WILL CONTAIN A FURTHER EXPLANATION AS TO WHY |
| | THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH THE |
| | PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW NOTE |
| | #1** |
| | |
| | B) A, OK, WILL HAVE NO COMMENTS EXCEPT PERHAPS A |
| | REFERENCE TO SEE ** NEW NOTES*. THE PREVIOUS REVIEW |
| | NOTE WILL BE REMOVED. |
| | |
| | C) A, NO/OK, WILL HAVE FURTHER EXPLANATION AS PART OF |
| | THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL. |
| | THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS |
| | REVIEW NOTE #1** |
| | |
| | D) NEW NOTES WILL BE ADDED TO THE END AND LABELED ** |
| | NEW NOTES ** |
| | |
| | |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE: NO. |
| | PLEASE SEE THERE WERE NO TIMES SUBMITTED. |
| | PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO NOT |
| | CORRELATE WITH THE FIXTURES, WATTAGES, THE NUMBER OF |
| | FIXTURES, AND THE TYPE OF FIXTURES ETC WHICH ARE ON |
| | PLANS. |
| | PLEASE SEE THE CALCULATIONS SUBMITTED AND COORDINATE |
| | WITH PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW#1** |
| | PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, .1.2 AND |
| | .1.3 |
| | PLEASE INDICATE SCHEDULING, OVER RIDE DEVICES AT |
| | INGRESS/EGRESS, SEPARATE SPACES, TIMES ON ALL OVER RIDE |
| | DEVICES. |
| | PLEASE SEE 13-415.1.AB.1, 13-415.2, AND 13-415.2.ABC.1 |
| | ENERGY CALCULATIONS ARE SUBMITTED HOWEVER THEY ARE NOT |
| | SIGNED, DATED OR SEALED BY THE ENGINEER OF RECORD. |
| | PLEASE CLARIFY PERFORMANCE CALCULATIONS AND HOW METHOD |
| | A CAN BE USED ON AN EXISTING SPACE OR IS THIS AN |
| | EXISTING SHELL WITH NEW EXTERIOR WALL BEING BUILD OUT |
| | FOR INTERIOR USE. |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE: NO, PLEASE SEE COMMENTS FROM FIRE REVIEW WHERE |
| | COOKING WITH GREASE LADEN VAPORS WHICH WILL REQUIRE A |
| | HOOD OF SORTS, AND AS THIS APPEARS TO BE THE CASE, |
| | ELECTRICAL FOR HOOD NEEDS TO BE SHOWN. THERE IS NOTHING |
| | LOCATED ON PLANS FOR SUCH AND ANY SHUT OFF OF ANY |
| | ELECTRICAL UNDER HOOD (WHERE ELECTRIC IS INSTALLED). |
| | PLEASE SEE COMMENT #7 WITH RESPECT TO MISSING |
| | CIRCUITING ON PLANS. |
| | |
| | **PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE SEE NFPA-96 AND CLARIFY ANY LIGHTING AND |
| | ELECTRICAL WHICH MAY BE PART OF ANY HOOD SYSTEM WHICH |
| | IS REQUIRED TO CONTAIN SHUNT TRIP DEVICES/BREAKERS. |
| | |
| | 5) NOTE: NO? NO NOTES, RESPONSE OR NOTES COULD BE FOUND |
| | AND PANELS SCHEDULE DOES NOT SEEM TO INDICATE ANY |
| | ELECTRICAL FOR THIS, NEW OR EXISTING. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE CLARIFY NEW OR EXISTING ROOF TOP GFI FOR THE RTU |
| | A/C SYSTEM. |
| | 210.63, 210.8 |
| | |
| | 6) NOTE: OK. |
| | |
| | 7) NOTE: NO. |
| | PLEASE SEE THERE ARE SEVERAL ITEMS ON PLANS WHICH DO |
| | NOT CORRELATE WITH THE PANEL SCHEDULES. |
| | PLEASE SEE THERE ARE ITEMS ON PANEL SCHEDULES NOT ON |
| | PLANS. |
| | PLEASE SEE THERE ARE ELECTRICAL ITEMS ON PLANS (LIGHTS) |
| | WHICH DO NOT INDICATE ANY CIRCUITING. |
| | PLEASE SEE PANEL SCHEDULE WHICH DOES NOT INCLUDE ALL |
| | CIRCUITS ON PLANS. |
| | PLEASE SEE ITEMS ON PANEL SCHEDULE SHOWN AS 220V , YET |
| | ON 1-POLE BREAKERS. |
| | ETC. |
| | ONE SET OF PLANS HAS MANY OF THESE ITEMS REDLINED, |
| | HOWEVER NOT ALL. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE PROVIDE ALL CIRCUITING ON PLANS AND CORRELATE |
| | WITH THE SUBMITTED PANEL SCHEDULE(S). PLEASE SEE SOME |
| | MISSING FOR LIGHTING, RECEPTS ETC. |
| | FBC 106.1.2, 106.3.5.1.2, NEC 408.4, 310.16 ETC |
| | |
| | 8) NOTE: NO, PLEASE SEE AS NOTE #7 ABOVE MENTIONS, |
| | PLEASE SEE FIXTURE(S) WHICH CIRCUITING IS MISSING. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE SEE 700.12 FOR CIRCUITING OF EMERGENCY AND EXIT |
| | LIGHTS. |
| | |
| | 9) NOTE: OK. |
| | |
| | 10) NOTE: OK. |
| | |
| | 11) NOTE: OK. |
| | |
| | 12) NOTE: |
| | |
| | 13) NOTE: OK. |
| | |
| | 14) NOTE: OK, VALUE INCREASED. |
| | |
| | 15) NOTE: OK. |
| | |
| | 16) NOTE: NO, SAME NOTE. PLEASE SEE THE FOLLOWING IS |
| | TEXT EXTRACTED FROM THE CODE TO HELP EXPLAIN THE |
| | PREVIOUS NOTE AS NO CHANGES WERE MADE TO THIS COMMENT. |
| | *SECTION 210.8(B)(2), WHICH WAS NEW FOR THE 2002 CODE, |
| | REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT RECEPTACLES IN |
| | NON-DWELLING-TYPE KITCHENS TO BE GFCI PROTECTED. THIS |
| | REQUIREMENT APPLIES TO ALL 15- AND 20-AMPERE, 125-VOLT |
| | KITCHEN RECEPTACLES, WHETHER OR NOT THE RECEPTACLE |
| | SERVES COUNTERTOP AREAS.* |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE SEE 210.8B3 FOR GFP PROTECTION FOR ALL 15/20A |
| | 120V RECEPTS IN KITCHEN/ KITCHEN AREAS. |
| | |
| | |
| | *** NEW NOTE ** |
| | |
| | 17) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTE GIVEN AT THIS TIME. |
| | ONE SET OF ELECTRICAL PLANS AND ENERGY CALCULATIONS ARE |
| | BEING RETAINED BY THIS OFFICE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |