| 2007-01-16 11:26:16 | *****DENIED***** |
| | |
| | |
| | 1. NFPA 101, 2003 EDITION, SHALL BE REFERENCED. |
| | |
| | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT |
| | INTERFERE OR HINDER EMERGENCY RESPNSE ACCESS TO THE |
| | SAID PROPERTY OR THE VICINITY THEREOF (INCLUDING FIRE |
| | LANES). |
| | |
| | 4.THE SUITE NUMBER WHERE THE SCOPE OF THE WORK WILL |
| | BE CONDUCTED SHOULD BE IN THE TITLE BLOCK OF THE |
| | SUBMITTED PLANS. |
| | |
| | 5.IT APPEARS THAT THE SCOPE OF WORK IS A CONVERSION |
| | FROM A BUSINESS OCCUPANCY TO A MERCANTILE OCCUPANCY. |
| | PLEASE BE ADVISED THAT THIS STRUCTURE SHALL BE |
| | CONSIDERED AS A NEW MERCANTILE OCCUPANCY. |
| | |
| | 6.IS OR WILL THE BUILDING/TENANT SPACE BE EQUIPPED |
| | WITH A FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM? |
| | |
| | 7.PROVIDE A LIFE SAFETY PLAN SHEET SHOWING THE TRAVEL |
| | DISTANCE TO REACH AN EXIT.THE LOCATION OF EXIT |
| | LIGHTS, EMERGENCY LIGHTS, AND FIRE EXTINGUISHERS MAY |
| | ALSO BE INCLUDED. |
| | |
| | 8.COMMERCIAL COOKING EQUIPMENT WHALL BE IN ACCORDANCE |
| | WITH NFPA 96.SEPARATE PLANS AND PERMIT WILL BE |
| | REQUIRED. |
| | |
| | 9.ON SHEET # 2.0E, LIGHTING PLAN, THERE ARE TWO EXITS |
| | NOTED.CORRECT THE FOLLOWING ISSUES:(1) THE FRONT |
| | EXIT DOOR WOULD NOT BE ABLE TO OPEN FULLY DUE TO THE |
| | FURINITURE (2) THERE IS A DOOR THAT OPENS INTO THE PATH |
| | OF THE REAR EXIT CORRIDOR. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, |
| | INCLUDE A RESPONSE SHEET INDICATING HOW/WHERE EACH ITEM |
| | WAS ADDRESSED. |
| | |
| | |