Plan Review Notes
Plan Review Notes For Permit 06120650
Permit Number 06120650
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-10 19:42:52** UNSAT **
  
 1) NOTE: PLEASE BE SURE ALL PLANS STATE THE FOLLOWING
 MINIMUM CODES IN WHICH PLANS ARE DESIGNED AND PERMITTED
 UNDER.
 PLEASE KNOW THE FOLLOWING WILL BE REQUIRED FOR
 ELECTRICAL SHEETS.
 2005 NFPA-70 *JUST AS AN FYI AS OF 12/8/06 THE STATE OF
 FLORIDA ADOPTED THE NEW 2005 NEC AND ANY PERMIT
 APPLICATIONS MADE FROM THAT DATE FORWARD WILL BE UNDER
 THE NEW CODE AND THE 2006 REVISIONS TO THE 2004 FBC.
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2 AND .1.3
 PLEASE INDICATE SCHEDULING, OVER RIDE DEVICES AT
 INGRESS/EGRESS, SEPARATE SPACES, TIMES ON ALL OVER RIDE
 DEVICES.
 PLEASE SEE 13-415.1.AB.1, 13-415.2, AND 13-415.2.ABC.1
 ENERGY CALCULATIONS ARE SUBMITTED HOWEVER THEY ARE NOT
 SIGNED, DATED OR SEALED BY THE ENGINEER OF RECORD.
 PLEASE CLARIFY PERFORMANCE CALCULATIONS AND HOW METHOD
 A CAN BE USED ON AN EXISTING SPACE OR IS THIS AN
 EXISTING SHELL WITH NEW EXTERIOR WALL BEING BUILD OUT
 FOR INTERIOR USE.
  
 3) NOTE: PLEASE SEE INFORMATION ON TITLE BLOCKS
 REFLECTS METRO DESIGN GROUP WHICH MUST BE LICENSED
 THROUGH THE STATE OF FLORIDA FOR PROVIDING ENGINEERING
 SERVICES.
 PLEASE SEE THAT THIS HAS BEEN NOTED ON PREVIOUS REVIEWS
 ON OTHER PROJECTS AND MAY BE SENT TO THE FLORIDA BOARD
 OF ENGINEERS FOR REVIEW.NO DETERMINATION FROM THE
 STATE HAS BEEN MADE AT THIS POINT IN TIME.
 FS 471.023, 481.229, FAC 61G15-23.002 ETC
 ONE SET OF PLANS WILL BE RETAINED BY THIS OFFICE AT
 THIS TIME.
  
 4) NOTE: PLEASE SEE NFPA-96 AND CLARIFY ANY LIGHTING
 AND ELECTRICAL WHICH MAY BE PART OF ANY HOOD SYSTEM
 WHICH IS REQUIRED TO CONTAIN SHUNT TRIP
 DEVICES/BREAKERS.
  
 5) NOTE: PLEASE CLARIFY NEW OR EXISTING ROOF TOP GFI
 FOR THE RTU A/C SYSTEM.
 210.63, 210.8
  
 6) NOTE: PLEASE SEE 220.12A FOR DETERMINING LOAD
 CALCULATIONS FOR SERVICE FEEDERS ON WINDOWS. PLEASE SEE
 QUOTED COMMENTARY.
 "THE 200-VOLT-AMPERE CALCULATION FOR EACH LINEAR FOOT
 OF A SHOW WINDOW IS REQUIRED TO DETERMINE THE FEEDER
 LOAD. SEE THE COMMENTARY FOLLOWING 220.3(B)(7) FOR LOAD
 CALCULATIONS FOR BRANCH CIRCUITS IN SHOW WINDOWS."
  
 7) NOTE: PLEASE PROVIDE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULE(S). PLEASE
 SEE SOME MISSING FOR LIGHTING, RECEPTS ETC.
 FBC 106.1.2, 106.3.5.1.2, NEC 408.4, 310.16 ETC
  
 8) NOTE: PLEASE SEE 700.12 FOR CIRCUITING OF EMERGENCY
 AND EXIT LIGHTS.
  
 9) NOTE: PLEASE SEE KITCHEN/KITCHEN PREP AND EAT IN
 AREAS SHALL CONTAIN A MINIMUM OF 1FT CANDLE FOR MEANS
 OF EGRESS TO THE PUBLIC RIGHT OF WAY. BASED ON THE TWO
 FIXTURES SHOWN THIS DOES NOT SEEM TO HAVE BEEN MET.
 PLEASE EITHER PROVIDE PHOTO-METRICS FOR EGRESS PATHS OR
 ADD AN ADDITIONAL TWO EMERGENCY LIGHT FIXTURES.
  
  
 10) NOTE: PLEASE PROVIDE MORE INFORMATION FOR THE
 EXISTING SERVICE.PLEASE SEE THE EXISTING SERVICE
 CONDUCTORS FROM THE GUTTER TO THE MAIN ARE SHOWN FOR A
 THREE PHASE SERVICE, YET RISER AND PANELS BOTH SHOW A
 SINGLE PHASE SERVICE.
 PLEASE COORDINATE.
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION.
  
 11) NOTE: PLEASE SEE RISER, RISER SHOWS A 200A PANEL
 "H", YET NO PANEL SCHEDULE HAS BEEN SUBMITTED FOR THIS.
 PLEASE SEE PANEL SCHEDULES SUBMITTED INDICATE A PANEL B
 AND A AND NO PANEL H IS SHOWN. PLEASE SEE PANEL B AND
 AS BEING 100A NOT 200AMP.
 PLEASE CLARIFY THE ENTIRE RISER FOR NEW AND EXISTING.
 FBC 106.1.2, 106.3.5.1.2
  
 12) NOTE: PLEASE SEE BASED ON THE PANEL SCHEDULE "A",
 CORRELATE THE FEEDERS AND OVER CURRENT PROTECTION WITH
 THE RISER. PANEL SCHEDULE SHOWS THIS A SINGLE POLE
 20AMP CIRCUIT.
 PLEASE SEE NEC 2005, 240.4, 310.16, 215.5 ETC
 FBC 106.3.5.1.2, 106.1.2
  
 13) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 THE EXISTING SERVICE AND THE NEW LOADS BEING ADDED.
 PLEASE SEE NEC 220,
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
 14) NOTE: PLEASE KNOW VALUE FOR COMPLETE SCOPE OF WORK
 SHALL INCLUDE ALL LABOR AND MATERIALS WHETHER OR NOT
 EQUIPMENT IS OWNER SUPPLIED. FBC ADMIN SECTION 108.3
  
 15) NOTE: PLEASE INDICATE A "FLOATING NEUTRAL" IS TO BE
 VERIFIED IN WHAT IS SHOWN AS AN EXISTING METER.
 REQUIRED FOR ALL METERS AFTER THE FIRST MEANS OF
 DISCONNECT. PLEASE SEE 250.6, AND 250.24B.
  
 16) NOTE: PLEASE SEE 210.8B3 FOR GFP PROTECTION FOR ALL
 15/20A 120V RECEPTS IN KITCHEN/ KITCHEN AREAS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]