| 2007-01-10 19:42:52 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE BE SURE ALL PLANS STATE THE FOLLOWING |
| | MINIMUM CODES IN WHICH PLANS ARE DESIGNED AND PERMITTED |
| | UNDER. |
| | PLEASE KNOW THE FOLLOWING WILL BE REQUIRED FOR |
| | ELECTRICAL SHEETS. |
| | 2005 NFPA-70 *JUST AS AN FYI AS OF 12/8/06 THE STATE OF |
| | FLORIDA ADOPTED THE NEW 2005 NEC AND ANY PERMIT |
| | APPLICATIONS MADE FROM THAT DATE FORWARD WILL BE UNDER |
| | THE NEW CODE AND THE 2006 REVISIONS TO THE 2004 FBC. |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, |
| | .1.2 AND .1.3 |
| | PLEASE INDICATE SCHEDULING, OVER RIDE DEVICES AT |
| | INGRESS/EGRESS, SEPARATE SPACES, TIMES ON ALL OVER RIDE |
| | DEVICES. |
| | PLEASE SEE 13-415.1.AB.1, 13-415.2, AND 13-415.2.ABC.1 |
| | ENERGY CALCULATIONS ARE SUBMITTED HOWEVER THEY ARE NOT |
| | SIGNED, DATED OR SEALED BY THE ENGINEER OF RECORD. |
| | PLEASE CLARIFY PERFORMANCE CALCULATIONS AND HOW METHOD |
| | A CAN BE USED ON AN EXISTING SPACE OR IS THIS AN |
| | EXISTING SHELL WITH NEW EXTERIOR WALL BEING BUILD OUT |
| | FOR INTERIOR USE. |
| | |
| | 3) NOTE: PLEASE SEE INFORMATION ON TITLE BLOCKS |
| | REFLECTS METRO DESIGN GROUP WHICH MUST BE LICENSED |
| | THROUGH THE STATE OF FLORIDA FOR PROVIDING ENGINEERING |
| | SERVICES. |
| | PLEASE SEE THAT THIS HAS BEEN NOTED ON PREVIOUS REVIEWS |
| | ON OTHER PROJECTS AND MAY BE SENT TO THE FLORIDA BOARD |
| | OF ENGINEERS FOR REVIEW.NO DETERMINATION FROM THE |
| | STATE HAS BEEN MADE AT THIS POINT IN TIME. |
| | FS 471.023, 481.229, FAC 61G15-23.002 ETC |
| | ONE SET OF PLANS WILL BE RETAINED BY THIS OFFICE AT |
| | THIS TIME. |
| | |
| | 4) NOTE: PLEASE SEE NFPA-96 AND CLARIFY ANY LIGHTING |
| | AND ELECTRICAL WHICH MAY BE PART OF ANY HOOD SYSTEM |
| | WHICH IS REQUIRED TO CONTAIN SHUNT TRIP |
| | DEVICES/BREAKERS. |
| | |
| | 5) NOTE: PLEASE CLARIFY NEW OR EXISTING ROOF TOP GFI |
| | FOR THE RTU A/C SYSTEM. |
| | 210.63, 210.8 |
| | |
| | 6) NOTE: PLEASE SEE 220.12A FOR DETERMINING LOAD |
| | CALCULATIONS FOR SERVICE FEEDERS ON WINDOWS. PLEASE SEE |
| | QUOTED COMMENTARY. |
| | "THE 200-VOLT-AMPERE CALCULATION FOR EACH LINEAR FOOT |
| | OF A SHOW WINDOW IS REQUIRED TO DETERMINE THE FEEDER |
| | LOAD. SEE THE COMMENTARY FOLLOWING 220.3(B)(7) FOR LOAD |
| | CALCULATIONS FOR BRANCH CIRCUITS IN SHOW WINDOWS." |
| | |
| | 7) NOTE: PLEASE PROVIDE ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH THE SUBMITTED PANEL SCHEDULE(S). PLEASE |
| | SEE SOME MISSING FOR LIGHTING, RECEPTS ETC. |
| | FBC 106.1.2, 106.3.5.1.2, NEC 408.4, 310.16 ETC |
| | |
| | 8) NOTE: PLEASE SEE 700.12 FOR CIRCUITING OF EMERGENCY |
| | AND EXIT LIGHTS. |
| | |
| | 9) NOTE: PLEASE SEE KITCHEN/KITCHEN PREP AND EAT IN |
| | AREAS SHALL CONTAIN A MINIMUM OF 1FT CANDLE FOR MEANS |
| | OF EGRESS TO THE PUBLIC RIGHT OF WAY. BASED ON THE TWO |
| | FIXTURES SHOWN THIS DOES NOT SEEM TO HAVE BEEN MET. |
| | PLEASE EITHER PROVIDE PHOTO-METRICS FOR EGRESS PATHS OR |
| | ADD AN ADDITIONAL TWO EMERGENCY LIGHT FIXTURES. |
| | |
| | |
| | 10) NOTE: PLEASE PROVIDE MORE INFORMATION FOR THE |
| | EXISTING SERVICE.PLEASE SEE THE EXISTING SERVICE |
| | CONDUCTORS FROM THE GUTTER TO THE MAIN ARE SHOWN FOR A |
| | THREE PHASE SERVICE, YET RISER AND PANELS BOTH SHOW A |
| | SINGLE PHASE SERVICE. |
| | PLEASE COORDINATE. |
| | FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION. |
| | |
| | 11) NOTE: PLEASE SEE RISER, RISER SHOWS A 200A PANEL |
| | "H", YET NO PANEL SCHEDULE HAS BEEN SUBMITTED FOR THIS. |
| | PLEASE SEE PANEL SCHEDULES SUBMITTED INDICATE A PANEL B |
| | AND A AND NO PANEL H IS SHOWN. PLEASE SEE PANEL B AND |
| | AS BEING 100A NOT 200AMP. |
| | PLEASE CLARIFY THE ENTIRE RISER FOR NEW AND EXISTING. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 12) NOTE: PLEASE SEE BASED ON THE PANEL SCHEDULE "A", |
| | CORRELATE THE FEEDERS AND OVER CURRENT PROTECTION WITH |
| | THE RISER. PANEL SCHEDULE SHOWS THIS A SINGLE POLE |
| | 20AMP CIRCUIT. |
| | PLEASE SEE NEC 2005, 240.4, 310.16, 215.5 ETC |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 13) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR |
| | THE EXISTING SERVICE AND THE NEW LOADS BEING ADDED. |
| | PLEASE SEE NEC 220, |
| | FBC ADMIN SECTION 106.1.2, 106.3.5.1.2 |
| | |
| | 14) NOTE: PLEASE KNOW VALUE FOR COMPLETE SCOPE OF WORK |
| | SHALL INCLUDE ALL LABOR AND MATERIALS WHETHER OR NOT |
| | EQUIPMENT IS OWNER SUPPLIED. FBC ADMIN SECTION 108.3 |
| | |
| | 15) NOTE: PLEASE INDICATE A "FLOATING NEUTRAL" IS TO BE |
| | VERIFIED IN WHAT IS SHOWN AS AN EXISTING METER. |
| | REQUIRED FOR ALL METERS AFTER THE FIRST MEANS OF |
| | DISCONNECT. PLEASE SEE 250.6, AND 250.24B. |
| | |
| | 16) NOTE: PLEASE SEE 210.8B3 FOR GFP PROTECTION FOR ALL |
| | 15/20A 120V RECEPTS IN KITCHEN/ KITCHEN AREAS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |