Plan Review Notes
Plan Review Notes For Permit 06120650
Permit Number 06120650
Review Stop B
Sequence Number 1
Notes
Date Text
2007-01-09 14:55:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)SHEET 1.0A NEW INTERIOR PARTITION, TEXT STATES
 FIRESTOP BUT NOTHING SHOWN GRAPHICALLY.
  
 3.)THE FLOOR PLAN SHOWS A TABLE BLOCKING THE FRONT
 DOOR.
  
 4.)DECLARE WIND DESIGN CRITERIA, FBC 1603.1.4.
  
 5.)PROVIDE PRODUCT APPROVALS FOR THE NEW WINDOWS.
 FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED
 FAC9B72.
  
 6.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 7.)INCLUDE FBC EB IN GOVERNING CODE.DECLARE LEVEL
 OF ALTERATION, FBC EB 3.
  
 8.)SEE FBC 11-4.1.6(2).SHOW COMPLIANCE ON THE PLAN.
 IF NECESSARY, PROVIDE COST INFORMATION.
  
 9.)IS THIS A CHANGE OF OCCUPANCY?WHAT IS THE
 OCCUPANCY OF THE ADJACENT TENANT?
  
 10.)SHEETS 3.1M AND 3.2M REFER TO THE WRONG BUILDING
 CODE (FBC2001).
  
 11.)ADDRESS ADDITTIONAL LOAD ON THE ROOF (MECHANICAL
 EQUIPMENT).
  
 12.)PROVIDE INFORMATION IN REGARDS TO HOW YOU
 DETERMINED OCCUPANT LOAD.SEE FBC 1004, CANNOT BE LESS
 THAN TABLE 1004.1.2.USING SQUARE FOOT AREA AND THE
 TABLE, M OCCUPANCY WOULD BE AN OCCUPANT LOAD OF 59. M
 IS FOR LESS THAN 50, OTHERWISE IS A AND NEEDS TWO MEANS
 OF EGRESS.PLEASE ADDRESS.
  
  
  
  
  
  