| 2007-01-09 14:55:21 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| | FBC2004 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO |
| | PERMIT PICKUP, FS713.13. |
| | |
| | 2.)SHEET 1.0A NEW INTERIOR PARTITION, TEXT STATES |
| | FIRESTOP BUT NOTHING SHOWN GRAPHICALLY. |
| | |
| | 3.)THE FLOOR PLAN SHOWS A TABLE BLOCKING THE FRONT |
| | DOOR. |
| | |
| | 4.)DECLARE WIND DESIGN CRITERIA, FBC 1603.1.4. |
| | |
| | 5.)PROVIDE PRODUCT APPROVALS FOR THE NEW WINDOWS. |
| | FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED |
| | FAC9B72. |
| | |
| | 6.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER |
| | OF RECORD, FBC*106.3.3. |
| | |
| | 7.)INCLUDE FBC EB IN GOVERNING CODE.DECLARE LEVEL |
| | OF ALTERATION, FBC EB 3. |
| | |
| | 8.)SEE FBC 11-4.1.6(2).SHOW COMPLIANCE ON THE PLAN. |
| | IF NECESSARY, PROVIDE COST INFORMATION. |
| | |
| | 9.)IS THIS A CHANGE OF OCCUPANCY?WHAT IS THE |
| | OCCUPANCY OF THE ADJACENT TENANT? |
| | |
| | 10.)SHEETS 3.1M AND 3.2M REFER TO THE WRONG BUILDING |
| | CODE (FBC2001). |
| | |
| | 11.)ADDRESS ADDITTIONAL LOAD ON THE ROOF (MECHANICAL |
| | EQUIPMENT). |
| | |
| | 12.)PROVIDE INFORMATION IN REGARDS TO HOW YOU |
| | DETERMINED OCCUPANT LOAD.SEE FBC 1004, CANNOT BE LESS |
| | THAN TABLE 1004.1.2.USING SQUARE FOOT AREA AND THE |
| | TABLE, M OCCUPANCY WOULD BE AN OCCUPANT LOAD OF 59. M |
| | IS FOR LESS THAN 50, OTHERWISE IS A AND NEEDS TWO MEANS |
| | OF EGRESS.PLEASE ADDRESS. |
| | |
| | |
| | |
| | |
| | |
| | |