| 2007-02-13 13:31:54 | BUILDING PLAN REVIEW |
| | PERMIT:06120649 |
| | ADD: 741 ROSELAND DR |
| | CONT: SLATUR CONST |
| | TEL: (954) 938-4500 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 1ST |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) 2004 FL. BLD CODE 1603.1.4 THE |
| | FOLLOWING INFORMATION RELATED TO WIND |
| | SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 3)110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | ) NUMBER OF UNITS |
| | ) NUMBER OF FLOORS |
| | ) NUMBER OF ROOMS |
| | ) NUMBER OF BEDROOMS |
| | ) SQ. FT. LIV SPACE/ FL |
| | ) SQ. FT. FOOTPRINT |
| | ) SQ. FT. UNDER ROOF (TOTAL) |
| | |
| | 4)106.1.2 ADDITIONAL DATA. THE |
| | BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS, |
| | STRESS DIAGRAMS, AND OTHER |
| | DATA NECESSARY TO DESCRIBE THE |
| | CONSTRUCTION OR INSTALLATION AND THE |
| | BASIS OF CALCULATION. ALL DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | REQUIRED BY THE BUILDING OFFICIAL TO BE |
| | PREPARED BY AN ARCHITECT OR ENGINEER |
| | SHALL BE AFFIXED WITH THIER OFFICIAL |
| | SEAL, SIGNATURE AND DATE AS STATE LAW |
| | REQUIRES. |
| | |
| | 5)WPB AMENDMENTS.106.1.3BUILDING PLANS SHALL BE |
| | DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL |
| | PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.THE BUILDING |
| | MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS |
| | FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| | CONFORMITY TO ITS RECORD RETENTION PROGRAM.THIS |
| | POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| | CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS |
| | MANAGEMENTS. THE DRAWINGS SHALL BE DRAFTSMAN QUALITY. |
| | THE DRAWINGS SUBMITTED ARE NOT ACCEPTABLE. |
| | |
| | 6)WILL THE CARPORT BE CONVERTED INTO A GARAGE OR |
| | LIVING SPACE? |
| | |
| | 7)106.1.1CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILINDING OFFICIAL |
| | |
| | 8)R309.1OPENINGS FROM A PRIVATE GARAGE DIRECTLY |
| | INTO A ROOM USED FOR SLEEPING PURPOSES SHALL NOT BE |
| | PERMITTED, OTHER OPENINGS BETWEEN THE GARAGE AND |
| | RESIDENCE SHALL BEEQUIPPED WITH SOLID WOOD DOORS NOT |
| | LESS THAN 1 3/8 INCHES IN THICKNESS, SOLID OR HONEYCOMB |
| | CORE STEEL DOORS NOT LESS THAN 1 3/8 INCHES THICK, OR |
| | 20-MINUTE FIRE-RATED DOORS. |
| | |
| | 9)R309.2THE GARAGE SHALL BE SEPERATED FROM THE |
| | RESIDENCE AND ITS ATTIC AREA BY NOT LESS THAN 1/2-INCH |
| | GYPSUM BOARD APPLIED TO THE GARAGE SIDE. GARAGES |
| | BENEATH HABITABLE ROOMS SHALL BE SEPERATED FROM ALL |
| | HABITABLE ROOMS ABOVE BY NOT LESS THAN 5/8-INCH TYPE X |
| | GYPSUM BOARD OR EQUIVALENT.WHERE THE SEPERATION IS A |
| | FLOOR-CEILING ASSEMBLY, THE STRUCTURE SUPPORTING THE |
| | SEPERATIION SHALL ALSO BE PROTECTED BY NOT LESS THAN |
| | 1/2 INCH GYPSUM BOARD OR EQUIVALENT. |
| | |
| | 10)R309.3THE AREA OF FLOOR USED FOR PARKING OF |
| | AUTOMOBILES OR OTHER VEHICLES SHALL BE SLOPED TO |
| | FACILICATE THE MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD |
| | THE MAIN VEHICLES SHALL BE SLOPED TO FACILITATE THE |
| | MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN |
| | VEHICLE ENTRY DOORWAY. |
| | |
| | 11)106.3.3* PRODUCT APPROVALS- 2004 |
| | THOSE PRODUCTS THAT ARE RGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITTING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. PROVIDE TWO SETS OF UPDATED |
| | PRODUCT APPROVALS FOR EACH PRODUCT. SUBMIT A |
| | WINDOW/DOOR SCHEDULE WITH THE SIZE OF EACH OPENING. ON |
| | A FLOOR PLAN INDICATE THE LOACTION OF EACH WINDOW OR |
| | DOOR OPENING. |
| | |
| | 12)IF THIS AREA WILL BE USED FOR LIVING SPACE, THE |
| | FLOOR WILL HAVE TO CONFORM TO THE REQUIREMENTS OF |
| | R506.1CONCRETE SLAB-ON-GROUND FLOORS SHALL BE A |
| | MINIMUM 3.5 INCHES (89 MM) THICK (FOR EXPANSIVE SOILS, |
| | SEE SECTION R403.1.8 ). THE SPECIFIED COMPRESSIVE |
| | STRENGTH OF CONCRETE SHALL BE AS SET FORTH IN SECTION |
| | R402.2 . |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |