Plan Review Notes
Plan Review Notes For Permit 06120643
Permit Number 06120643
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-02-15 18:15:51*****DENIED*****
  
  
 1.THE ADDRESS ON THE SUBMITTED PLAN SHEETS DO NOT
 CORRELATE WITH THAT IN THE ADDRESS ASSOCIATED WITH THIS
 PERMIT.
  
 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 3.THE GENERATOR FOR EMERGENCY USE OR STANDBY POWER
 SHALL BE INSTALLED, TESTED, AND MAINTAINED IN
 ACCORDANCE WITH NFPA 110.
  
 4.INDICATE THE DISTANCE OF THE GENERATOR TO THE ANY
 OPENINGS IN THE BUILDING.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A, WILLIAMS
 FIRE PLAN REVIEW