| 2007-01-19 15:30:15 | *****DENIED***** |
| | |
| | |
| | PLEASE BE ADVISED THAT THIS STRUCTURE SHALL BE |
| | CLASSIFIED AS A NEW BUSINESS OCCUPANCY. |
| | |
| | |
| | 01.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE |
| | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. |
| | |
| | 02.THE SET-UP OR ERECTING OPERATIONS FOR THE |
| | STRUCTURE SHALL NOTINTERFERE OR HINDER EMERGENCY |
| | RESPONSE ACCESS TO THE SAID PROPERTY OR VICINITY |
| | THEREOF (INCLUDING FIRE LANES). |
| | |
| | 03.FIRE DEPARTMENT ACCESS ROADSSHALL BE CAPABLE OF |
| | SUPPORTING 32 TONS TO SUPPORT THE LOADS IMPOSED BY FIRE |
| | APPARATUS/FIRE EQUIPMENT AND SHALL BE PROVIDED WITH A |
| | SURFACE SUITABLE FOR ALL-WEATHER DRIVING CONDITIONS. |
| | |
| | 04.FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN |
| | UNOBSTRUCTED WIDTH OF NOT LESS THAN 20' AND AN |
| | UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13' |
| | 6IN". |
| | |
| | 05.SHOW/DISPLAY THE NUMERICAL ADDRESS OF THE |
| | STRUCTURE ON THE PROPER EXTERIOR ELEVATION.AS PER |
| | WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS |
| | THAN 6" IN HEIGHT AND 1" IN WIDTH VISIBLE FROM THE |
| | STREET OR ROADSIDE FRONTING THE STRUCTURE.[THE |
| | APPLICABLE ADDRESS SHALL BE IN THE TITLE BLOCK OF EACH |
| | SUBMITTED PLAN SHEET]. |
| | |
| | 06.INDICATE ON SITE PLAN THE DISTANCE OF THE |
| | STRUCTURE TO THE NEAREST FIRE HYDRANT.PLEASE BE |
| | ADVISED THAT IF THIS DISTANCE IS GREATER THAN 500 FEET, |
| | AN ADDITIONAL FIRE HYDRANT MAY BE REQUIRED. |
| | |
| | 07.WILL THE STRUCTURE HAVE A FIRE ALARM AND/OR FIRE |
| | SPRINKLER SYSTEM?IF SO, PLEASE PROVIDE A LAYOUT OF |
| | THE FIRE PROTECTION SYSTEM(S). |
| | |
| | 08.WHAT IS THE MAXIMUM OCCUPANT LOAD FOR THE |
| | STRUCTURE? |
| | |
| | 09.INDICATE THE LOCATION OF EXIT LIGHTS, EMERGENCY |
| | LIGHTS, AND FIRE EXTINGUISHER(S). |
| | |
| | 10.PLEASE INDICATE THE LENGHT OF TIME THAT THIS |
| | TEMPORARY STRUCTURE WILL BE USED. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, |
| | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH |
| | ITEM WAS ADDRESSED ON THE PLANS. |
| | |
| | |
| | MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |