| Plan Review Notes For Permit 06120634 |
| Permit Number |
06120634 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-10-08 16:04:28 | *****REVISION DENIED***** | | | | | | 1. THE SUBMITTED REVISED PLAN SHEETS FP-1 & FP-2 DO NOT | | | CORRELATE WITH THE SHEETS FP-1 & FP-2 ON FILE WITH | | | CONSTRUCTION SERVICES DEPARTMENT. IT WOULD APPEAR THAT | | | THE REVISIONS CORRELATE WITH SHEET FP-27 & FP-28 OF THE | | | PERMITTED PLAN SET. | | | | | | 2. IN THE PERMITTED PLAN SET, JOHN OLSEN IS RECORDED AS | | | THE PROFESSIONAL ENGINEER WHEREAS THE REVISED SHEETS | | | HAS ROBERT ANTHONY DUNLEA. PROVIDE DOCUMENTATION THAT | | | THERE HAS BEEN AN ENGINEER OF RECORD CHANGE. | | | | | | 3. IT APPEARS THAT THE PROFESSIONAL ENGINEER'S | | | SIGNATURE HAS BEEN RUBBER STAMPED. PLEASE REFERENCE | | | FLORIDA STATUTE 471.025 AND FLORIDA ADMINISTRATIVE CODE | | | 61G15-23.002 | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|