2007-01-20 17:30:36*****UNSAT*****
  
  
 1.THE DATA FOR THE STANPIPE SHOWS A SAFETY MARGIN OF
 ONLY 4.462 PSI.AS PER WEST PALM BEACH FIRE
 PREVENTION, A SAFETY MARGIN OF AT LEAST 5.0 IS
 REQUIRED.
  
 *REMINDERS*
  
 2.FIRE SPRINKLER SYSTEM IN CONJUNCTION WITH THE FIRE
 ALARM SYSTEM IS TO BE FULLY MONITORED.
  
 3. AS PER WEST PALM BEACH FIRE PREVENTION, A WATERFLOW
 SHALL ACTIVATE A GENERAL FIRE ALARM WITHIN 45 TO 60
 SECONDS.
  
 4. COORDINATE WITH THE GENERAL AND/OR FIRE ALARM
 CONTRACTOR THAT THE DOUBLE CHECK VALVE DETECTOR BE
 CHAINED AND LOCKED UPON THE COMPLETION OF THE FIRE
 ALARM FINAL.
  
 5.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  