| Plan Review Notes For Permit 06120634 |
| Permit Number |
06120634 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-20 17:30:36 | *****UNSAT***** | | | | | | | | | 1.THE DATA FOR THE STANPIPE SHOWS A SAFETY MARGIN OF | | | ONLY 4.462 PSI.AS PER WEST PALM BEACH FIRE | | | PREVENTION, A SAFETY MARGIN OF AT LEAST 5.0 IS | | | REQUIRED. | | | | | | *REMINDERS* | | | | | | 2.FIRE SPRINKLER SYSTEM IN CONJUNCTION WITH THE FIRE | | | ALARM SYSTEM IS TO BE FULLY MONITORED. | | | | | | 3. AS PER WEST PALM BEACH FIRE PREVENTION, A WATERFLOW | | | SHALL ACTIVATE A GENERAL FIRE ALARM WITHIN 45 TO 60 | | | SECONDS. | | | | | | 4. COORDINATE WITH THE GENERAL AND/OR FIRE ALARM | | | CONTRACTOR THAT THE DOUBLE CHECK VALVE DETECTOR BE | | | CHAINED AND LOCKED UPON THE COMPLETION OF THE FIRE | | | ALARM FINAL. | | | | | | 5.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE | | | DEPARTMENT CONNECTIONS. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | | ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|