| Plan Review Notes For Permit 06120629 |
| Permit Number |
06120629 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-09-17 11:07:37 | BUILDING PROVISO | | | | | | THE PLANS SPECIFY EXPOSURE CATEGORY "C". SUBMIT RAS 117 | | | CALCULATIONS FOR THE GAF MODIFIED ROOFING SYSTEM WITH | | | ENHANCED FASTENING THAT IS CAPABLE OF RESISTING THE | | | COMPONENT AND CLADDING PRESSURES FOR ROOFS IN EXPOSURE | | | "C" WITH A 140 MPH (3 SECOND GUST) WIND SPEED. THE ONES | | | THAT WERE SUBMITTED ARE INCORRECT. |
|