| 2007-06-22 08:14:48 | DENIED 2ND TIME |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OFDENIED REFERENCE: |
| | FBC-2004 PLUMBING, FBC-2004 CHAPTER 1, CITY OF WEST |
| | PALM BEACH AMENDMENTS, AND FLORIDA ADMINISTRATIVE |
| | CODE. |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| | MADE ON PREVIOUS REVIEWS. |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| | PREVIOUS REVIEW NOTES. |
| | |
| | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| | |
| | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| | |
| | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN |
| | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| | COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| | |
| | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| | |
| | 1. **NO**FBC-2004 CHAPTER 1,SECTION 106.3.4.3: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME. IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND |
| | 417 FS, RESPECTIVELY. |
| | |
| | 2. **OK** |
| | |
| | 3. **NO/OK** SHEET M/P/E-1 WATER HEATER DETAIL, THE |
| | FOLLOWING IS STILL REQUIRED AND NEEDS TO BE SHOWN ON |
| | THE RESUBMITTAL: |
| | A} **OK** |
| | B} **OK** |
| | C} **OK** |
| | D} **OK** |
| | E} **OK** |
| | F} **OK** |
| | G} **OK** |
| | H} **NO** PER FBC-2004 PLUMBING, SECTION 607.3, |
| | THERMAL EXPANSION CONTROL REQUIRED. PLEASE ADD THE |
| | THERMAL EXPANSION PROTECTION ON THE RESUBMITTED WATER |
| | HEATER DETAIL. |
| | |
| | THE FOLLOWING ARE NEW ITEMS: |
| | |
| | 4. SHEET M/P/E-1 ELECTRIC WATER HEATER DETAIL: THE |
| | NEWLY SUBMITTED ELECTRIC WATER HEATER DETAIL IS |
| | INDICATING A BOTTOM FED WATER HEATER. PLEASE ADD THE |
| | FOLLOWING FOR THIS HEATER PER FBC-2004 PLUMBING, |
| | SECTION 504.2 A BOTTOM FED WATER HEATER SHALL HAVE A |
| | VACUUM RELIEF VALVE INSTALLED. THE VACUUM RELIEF SHALL |
| | COMPLY WITH ANSI Z21.22. PLEASE INDICATE THIS ON THE |
| | RESUBMITTAL. |
| | |
| | 5. SHEET M/P/E-1 PLUMBING RISER: THE RESUBMITTED |
| | ISOMETRIC RISER DIAGRAM IS INDICATING A 4" X 4" X 3" |
| | COMBINATION-WYE AND EIGHTH BEND TO THE WATER CLOSET. |
| | PLEASE DELETE THIS AND THE OFFSET TO THE WATER CLOSET |
| | AND ADD A 4" QUARTER BEND IN ITS PLACE FOR THE |
| | RESUBMITTAL. |
| | |
| | **********IMPORTANT INFORMATION |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |