| 2007-07-09 15:42:29 | DENIED BY BUILDING |
| | |
| | 1) THE NOC THAT WAS SUBMITTED IS EXPIRED. IT WILL NEED |
| | TO BE RERECORDED BEFORE THE PERMIT IS ISSUED. |
| | |
| | 2) SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY |
| | IMPACT FEES. ATTACH THE SHEETS WITH THE COUNTY IMPACT |
| | FEE STAMPS FROM THE OLD PLANS TO THE FRONT OF THE NEW |
| | PLANS OR HAVE THE NEW PLANS STAMPED BY THE COUNTY. |
| | |
| | 3) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED |
| | BY THE PREPARER PER FBC CHAPTER 13. |
| | |
| | 4) BATHROOM DOOR NUMBER 10 ON THE SCHEDULE DOES NOT |
| | COMPLY WITH R322.1.1 FOR ACCESSIBILITY, WHICH REQUIRES |
| | AT LEAST ONE BATHROOM WITH A DOOR THAT HAS A 29" CLEAR |
| | OPENING. |
| | THE 29 " CLEAR OPENING IS WITH THE DOOR OPEN 90 DEGREES |
| | MEASURED BETWEEN THE FACE OF THE DOOR AND THE OPPOSITE |
| | STOP. SEE R322.2.2 AND FBC 11-4.13.5. |
| | |
| | 5) THE TRUSS LAYOUT IS REQUIRED TO BE SIGNED, SEALED |
| | AND DATED BY THE TRUSS ENGINEER, IN ADDITION TO BEING |
| | REVIEWED AND APPROVED BY THE DESIGNER OF RECORD FOR THE |
| | STRUCTURE. |
| | FS 471 |
| | |
| | 6) THE TRUSS DRAWINGS ARE REQUIRED TO BE SIGNED BY THE |
| | TRUSS ENGINEER, SIGNATURE STAMPS ARE NOT ACCEPTABLE. FS |
| | 471 AND FAC 61G15-23.002. |
| | NOTE: TRUSS LAYOUT AND DRAWINGS CAN BE SUBMITTED THE |
| | INSPECTOR IN THE FIELD AT TIME OF TRUSS INSPECTION. |
| | |
| | 7) SPECIFY WHICH ONE OF THE FASTENING OPTIONS AND |
| | DESIGN PRESSURES ON PAGE 28 OF THE NOAWILL BE USED TO |
| | INSTALL THE GAF MODIFIED ROOF SYSTEM. CIRCLE THE |
| | APPROPRIATE ONE ON THE NOA. THE DESIGN PRESSURES ARE |
| | LESS THAN REQUIRED FOR A FLAT ROOF IN ZONE C ( -107.7 |
| | PSF FOR ROOF ZONE 3 AND - 71.6 FOR ZONE 2) . SUBMIT RAS |
| | 117 CALCULATIONS FOR ENHANCED FASTENING AS ALLOWED BY |
| | LIMITATION #7 ON PAGE 32 OF THE NOA. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |