| Date |
Text |
| 2007-01-18 12:10:44 | *** DENIED *** |
| | 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC |
| | 13-101.2.2. |
| | |
| | 2) PLEASE SUBMITMANUAL J CALCULATIONS, PER 2004 FBC |
| | 13-607.1.ABC.1 . |
| | |
| | 3) SEE ONE SET OF PLANS PAGE M/P/E-1 HAS AN ENGINEER'S |
| | NAME AND INFORMATION IN THE TITLE BLOCK , SO HIS |
| | SIGNATURE AND SEAL MUST ALSO APPEAR IN THE TITLE BLOCK, |
| | PER FAC 61G15-23.002. |
| | |
| | 4) PLEASE SHOW AN EQUIPMENT (A/C) LISTING WITH ALL |
| | PERTINENT INFORMATION ON THE MECHANICAL PLANS. |
| | |
| | 5) THE RETURN AIR GRILL CAN NOT BE LOCATED IN THE |
| | MASTER BATHROOM, PER 2004 FBC/R M1602.2(4), PLEASE |
| | CORRECT. |
| | |
| | 6) THE MASTER BATHROOM WITH THE TUB WILL REQUIRE AN |
| | EXHAUST FAN, PER 2004 FBC/R R303.3, PLEASE CORRECT. |
| | |
| | 7) PLEASE SHOW THE SIZE OF ALL SUPPLY AND RETURN AIR |
| | GRILLS ON PLANS. |
| | |
| | 8) PLEASE SHOW THE SIZE OF THE RETURN AIR DUCT (FLEX) |
| | ON MECHANICAL PLANS. |
| | |
| | *** INFORMATIONAL *** |
| | BALANCED RETURN AIR MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |