2007-09-28 10:25:27REVISION TO MECH. PLANS PAGE AC-1 &AC-2.
 *** PROVISO ***
 1)2004 F.B.C/M 307.2.3(1).AN AUXILIARY DRAIN PAN
 WITH A SEPARATE DRAIN SHALL BE PROVIDED UNDER THE COILS
 ON WHICH CONDENSATION WILL OCCUR. THE AUXILIARY PAN
 DRAIN SHALL DISCHARGE TO A CONSPICUOUS POINT OF
 DISPOSAL TO ALERT OCCUPANTS IN THE EVENT OF A STOPPAGE
 OF THE PRIMARY DRAIN. THE PAN SHALL HAVE A MINIMUM
 DEPTH OF 1.5 INCHES, SHALL NOT BE LESS THAN 3 INCHES
 LARGER THAN THE UNIT OR THE COIL DIMENSIONS IN WIDTH
 AND LENGTH AND SHALL BE CONSTRUCTED OF
 CORROSION-RESISTANT MATERIAL. METALLIC PANS SHALL HAVE
 A MINIMUM THICKNESS OF NOT LESS THAN 0.0276-INCH
 GALVANIZED SHEET METAL. NONMETALLIC PANS SHALL HAVE A
 MINIMUM THICKNESS OF NOT LESS THAN 0.0625 INCH.