2007-03-06 10:50:37 
 DENIED/INCOMPLETE INFORMATION
  
 THE INPUT DATA REPORT INDICATES 1 LUMINAIRE @ 1910
 WATTS. PLEASE INDICATE COMPLIANCE WITH ALL FIXTURES TO
 BE USED. ALSO SUBMIT A LEGEND OF FIXTURE TYPES AND
 WATTAGES ON THE PLAN TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  