| Plan Review Notes For Permit 06120620 |
| Permit Number |
06120620 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-17 07:52:35 | DENIED; | | | 1.BREAK SINK TO BE HANDICAP ACCESSIBILE MUST COMPLY | | | WITH FBC-2004 BUILDING CHAPTER 11. SEE SECTIONS | | | 11-4.24.2 THRU 7. SHOW DETAIL ON PLANS SHOWING ALL | | | MEASUREMENTS REQUIRED. SHOW CLEAR FLOOR SPACE ON FLOOR | | | PLAN AT BREAK SINK (FRONTAL APPROACH REQUIRED). | | | 2.WATER ISOMETRIC, A WATER HAMMER ARRESTOR IS REQUIRED | | | FOR ICE MACHINE. SPEC. OUT MANUFACTURE AND SIZE LIST ON | | | PLANS, AND SHOW ON ISOMETRIC. TO BE INSTALLED AS CLOSE | | | TO SOURCE AS PASSIBLE. FBC-2004 PLUMBING SECTION | | | 604.9. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|