2007-01-17 07:52:35DENIED;
 1.BREAK SINK TO BE HANDICAP ACCESSIBILE MUST COMPLY
 WITH FBC-2004 BUILDING CHAPTER 11. SEE SECTIONS
 11-4.24.2 THRU 7. SHOW DETAIL ON PLANS SHOWING ALL
 MEASUREMENTS REQUIRED. SHOW CLEAR FLOOR SPACE ON FLOOR
 PLAN AT BREAK SINK (FRONTAL APPROACH REQUIRED).
 2.WATER ISOMETRIC, A WATER HAMMER ARRESTOR IS REQUIRED
 FOR ICE MACHINE. SPEC. OUT MANUFACTURE AND SIZE LIST ON
 PLANS, AND SHOW ON ISOMETRIC. TO BE INSTALLED AS CLOSE
 TO SOURCE AS PASSIBLE. FBC-2004 PLUMBING SECTION
 604.9.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695