Plan Review Notes
Plan Review Notes For Permit 06120620
Permit Number 06120620
Review Stop M
Sequence Number 1
Notes
Date Text
2007-01-11 14:18:17*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) RETURN AIR TRANSFER DUCT FROM LISA'S OFFICE #107 IS
 GOING TO THE SUPPLY AIR TRUNK LINE IN CORRIDOR #104,
 PLEASE CORRECT.
  
 3) 14" RETURN AIR TRANSFER DUCT FROM CONFERENCE ROOM
 #103 TO CORRIDOR #102, AND LISA'S OFFICE #107 TO
 CORRIDOR #104 NEED TO BE 18".
 BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE. SEE 2004 FBC/M 601.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.