| Plan Review Notes For Permit 06120620 |
| Permit Number |
06120620 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-11 14:18:17 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 2) RETURN AIR TRANSFER DUCT FROM LISA'S OFFICE #107 IS | | | GOING TO THE SUPPLY AIR TRUNK LINE IN CORRIDOR #104, | | | PLEASE CORRECT. | | | | | | 3) 14" RETURN AIR TRANSFER DUCT FROM CONFERENCE ROOM | | | #103 TO CORRIDOR #102, AND LISA'S OFFICE #107 TO | | | CORRIDOR #104 NEED TO BE 18". | | | BALANCED RETURN AIR MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. SEE 2004 FBC/M 601.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|