| Plan Review Notes For Permit 06120620 |
| Permit Number |
06120620 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-17 10:54:59 | ***DENIED*** | | | | | | 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE | | | SAFETY SHALL COMPLY WITH NFPA 101, 2003 EDITION. PLEASE | | | ADD TO CODE ANALYSIS. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE | | | SPRINKLER REMODEL IN ADDITION TO FIRE ALARM. | | | | | | 3) NEW DUCT SMOKE DETECTORS SHALL BE WIRED TO FIRE | | | ALARM AND CAUSE A GENERAL FIRE ALARM IN ACCORDANCE WITH | | | LOCAL REQUIREMENTS. | | | | | | 4) PLEASE SHOW LOCATIONS OF 2A-10B,C RATED FIRE | | | EXTINGUISHERS THAT SHALL NOT EXCEED 75' TRAVEL DISTANCE | | | TO REACH. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | (561) 805-6722 OR 804-4756 |
|