| Plan Review Notes For Permit 06120599 |
| Permit Number |
06120599 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-02-01 18:13:19 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | 1.)FIRST APPLICATION USED THE MOST STRINGENT | | | CONDITION FOR DESIGN PRESSSURES, FULLY ENCLOSED.IN | | | THE NEW ENGINEERING YOU HAVE CIRCLED BOTH BUT HAVE | | | WRITTEN THE LESS STRINGENT CONDITION ON THE | | | INSTALLATION SCHEDULE.IF YOU ARE TO USE THE LESS | | | STRINGENT PRESSURES, SEE ENGINEER'S NOTE 2G.THIS IS | | | TO BE DETERMINED BY AN ARCHITECT OR ENGINEER. | | | CALCULATIONS SHOWING THAT THIS IS A PARTIALLY ENCLOSED | | | BUILDING WILL BE REQUIRED FOR YOU TO USE THESE | | | PRESSURES. | | | |
|