Plan Review Notes
Plan Review Notes For Permit 06120598
Permit Number 06120598
Review Stop B
Sequence Number 1
Notes
Date Text
2007-02-09 19:00:18BUILDING PLAN REVIEW
 PERMIT: 06120598
 ADD:516 34TH STREET
 CONT:OWNER
 TEL: (561)841-5365
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4)106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.PROVIDE PRODUCT APPROVALS FOR
 WINDOWS/ DOORS/ SHUTTERS/ROOFING MATERIALS ETC.
  
 5)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 IS REQUIRED.
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) NUMBER OF BEDROOMS
 ) SQ. FT. LIV SPACE/ FL
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) FLOOD ZONE
 ) FLOOD ELEVATION
 )L.O.M.R.
  
 6)R401.3 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF
 COLLECTION SO AS TO NOT CREATE A HAZARD. LOTS SHALL BE
 GRADED SO AS TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE AWAY FROM FOUNDATION WALLS
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
  
 7)FS.481.221ALL FINAL CONSTRUCTION DOCUMENTS AND
 DRAWINGS, PLANS, SPECIFICATIONS, OR REPORTS PREPARED OR
 ISSUED BY THE REGISTERED ARCHITECT AND BEING FILED FOR
 PUBLIC RECORD SHALL BEAR THE SIGNATUREAND SEAL OF THE
 REGISTERED ARCHITECT WHO PREPARED OR APPROVED THE
 DOCUMENTS AND THE DATE ON WHICH THEY WERE SEALED. THE
 SIGNATURE, DATE, AND SEAL SHALL BE EVIDENCE OF THE
 AUTHENTICITY OF THAT TO WHICH THEY ARE AFFIXED. THE
 SEAL IS NOT CLEAR ON ALL SHEETS.
  
 8)R802.1.6 TRUSS DESIGN DRAWINGS SHALL INCLUED, AT A
 MINIMUM, THE INFORMATION SPECIFIED IN THIS SECTION.
 PROVIDE A ROOF FRAMING DETAIL DRAWINGS WITH THE
 CONCENTRATED LOAD/ CONNECTION REQUIREMENTS/ CALCULATED
 DEFLECTION RATIO AND/OR MAXIMUM DESCRIPTION FOR LIVE
 AND TOTAL LOAD/DESIGN WIND SPEED AND EXPOSURE
 CATEGORY/SLOPE OR DEPTH, SPAN AND SPACING/LUMBER SIZE,
 SPECIES AND GRADE FOR EACH MEMBER ETC.
  
 9)R803.2.3.1 WOOD STRUCTURAL PANEL SHEATHING SHALL BE
 FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6
 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT
 INTERMEDIATE FRAMING. HOWEVER, WHERE ROOF FRAMING WITH
 ASPECIFIC GRAVITY, 0.42_< G< 0.49 IS USED, SPACING OF
 RING-SHANK FASTENERS SHALL BE 4 INCHES ON CENTER IN
 NAILING ZONE 3 FOR 130 MPH OR GREATER DESIGN WIND
 SPEEDS IN ACCORDANCE WITH FIGURE R803.2.3.1
  
 10)THE WALL TYPE LEGEND STATES THAT BOTH WALLS ARE
 NON-BEARING WALLS. INDICATE ON THE DRAWINGS WHERE THE
 BEARING WALLS ARE LOCATED. TO SUPPORT THE ROOF.
  
 11)WILL THERE BE ADDITIONAL SUPPORT ADDEDTO CARRY
 THE WEIGHT OF THE NEW AHU-2? IF SO, SUBMIT A DETAIL
 DRAWINGSHOWING HOW THE EQUIPMENT WILL BE SUPPORTED.
  
 12)R806.1 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES
 FORMED WHERE CEILINGS AR APPLIED DIRECTLY TO THE
 UNDERSIDE OF ROOF RAFTERS SHALL HAVE CROSS VENTILATION
 FOR EACH SEPARATE SPACE BY VENTILATING OPENINGS
 PROTECTED AGAINST THE ENTRANCE OF RAIN. VENTILATING
 OPENINGS SHALL BE PROVIDED WITH CORROSION-RESISTANT
 WIRE MESH, WITH 1/8 INCH MAXIMUM OPENINGS.
  
 13)R703.2 ASPHALT-SATURATED FELT FREE FROM HOLES AND
 BREAKS, WEIGHING NOT LESS THAN 14 POUNDS PER 100 SQUARE
 FEET AND COMPLYING WITH ASTM D 226 OR OTHER APPROVED
 WEATHER-RESISTANT MATERIAL SHALL BE APPLIED OVER STUDS
 OR SHEATHING OF ALL EXTERIOR WALLS AS REQUIREDBY TABLE
 R703.4. SUCH FELT OR MATERIAL SHALL BE APPLIED
 HORIZONTALLY, WITH THE UPPER LAYER LAPPED OVER THE
 LOWER LAYER NOT LESS THAM 2 INCHES. WHERE JOINTS OCCUR,
 FELT SHALL BE LAPPED NOT LESS THAN 6 INCHES.
  
 14)R319.1 WOOD JOISTS OR THE BOTTOM OF A WOOD
 STRUCTURAL FLOOR WHEN CLOSER THAN 18 INCHES OR WOOD
 GIRDERS WHEN CLOSER THAN 12 INCHES TO THE EXPOSED
 GROUND IN CRAWL SPACES OR UNEXCAVATED AREA LOCATED
 WITHIN THE PERIPHENCY OF THE BUILDING FOUNDATION, SHALL
 REQUIRE TO BE OF AN APPROVED SPECIES AND GRADE OF
 LUMBER, PRESSURE TREATED IN ACCORDANCE WITH AWPACI, OR
 DECAY-RESISTANT HEARTWOOD OF REDWOOD, BLACK LOCUST, OR
 CEDARS.SEE SHEET A-7 DETAIL #1 WHICH IS MISSING ALL
 DIMENTIONS RELATED TO THE STEM WALL. ARE THE FOOTERS
 BELOW GRADE? IF THEY ARE PLEASE INDICATE THE DIMENTIONS
 ON THE DRAWINGS.
  
 15)R408.1 THE UNDER-FLOOR SPACE BETWEEN THE BOTTOM OF
 THE FLOOR JOISTS AND THE EARTH UNDER ANY BUILDING SHALL
 BE PROVIDED WITH VENTILATION OPENINGS THROUGH
 FOUNDATIONS WALLS OR EXTERIOR WALLS. ONE SUCH
 VENTILATING OPENING SHALL BE WITHIN 3FEET OF ?EACH
 CORNER? OF SAID BUILDING.
  
 16)R408.3 ACCESS SHALL BE PROVIDED TO ALL UNDER-FLOOR
 SPACES. ACCESS OPENINGS THROUGH THE FLOOR SHALL BE A
 MINIMUM OF 18 INCHES BY 24 INCHES. OPENINGS THROUGH A
 PERIMETER WALL SHALL BE 16 INCHES BY 24 INCHES. SHOW
 COMPLIANCE.
  
 17)PROVIDE A WINDOW AND DOOR HEADDER FRAMING DETAIL
 ON THE DRAWINGS. SEE INFORMATION IN PACKAGE FOR HEADERS
 AROUND WALL OPEINGS.
  
 18)TO DETERMINE THE NUMBER AND SIZE OF ROOF DRAINS
 REQUIRED, SHOW THE HEIGHT OF THE PARAPET WALL FROM THE
 ROOF DECK TO THE TOP OF THE PARAPET WALL.. ALSO STATE
 THE SQUARE FOOTAGE OF THE ROOF AND SEE SEC.R903 FOR
 MORE INFORMATION.
  
 19) NOTE: R-19 INSULATION WILL NOT FIT WITH THE 2 X 4
 STUD.
  
 20)SHOW THE CONNECTION DETAIL FROM THE FOUNDATION TO
 THE WALL FRAMING INDICATINT THE ALL CONNECTION STRAPS.
 ALSO SHOW IN DETAIL HOW THE NEW ROOF WILL TIE INTO THE
 EXISTING HOUSE.
  
 21)R602.1.2FIREBLOCKING SHALL BE PROVIDED TO CUT
 OFF ALL CONCEALED DRAFT OPENINGS AND TO FORM AN
 EFFECTIVE FIRE BARRIER BETWEEN THE WALLS AND ROOF
 SPACE. SHOW COMPLIANCE.
  
 MYRON JACOBS
 BUILDING PLANS EXAMINER
 (561) 805-6726
  
  
  
  
  
  
  
  
  
  
  