| 2007-02-06 14:12:17 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT A-03 SHOW THE CLEAR FLOOR SPACE FOR THE KITCHEN |
| | SINK PER SECTION 11-4.24.5. FORWARD APPROACH REQUIRED |
| | AND SHALL EXTEND A MAXIMUM 19" UNDERNEATH THE SINK. |
| | CABINET DOORS ARE NOT ALLOWED IN THE CLEAR FLOOR SPACE |
| | OF THE SINK. DELETE FROM CABINET DETAIL. |
| | |
| | 2. SHT A-08 DETAIL. SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | A. 11-4.24.2 HEIGHT |
| | B. 11-4.24.3 KNEE CLEARANCE |
| | C. 11-4.24.4 SINK DEPTH |
| | D. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | F. 11-4.24.7 FAUCETS |
| | |
| | 3. SHT P0.1 WATER RISER DIAGRAM. THE WATER HAMMER |
| | ARRESTOR SHALL BE LOCATED NEAR THE FIXTURE, IN AN |
| | "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH |
| | 201 AND MANUF. INSTALLATION INSTRUCTIONS. (ALSO SEE |
| | PLUMBING NOTE #13). |
| | |
| | 4. ALL ARCHITECTURAL SHEETS. A TITLE BLOCK MUST APPEAR |
| | ON ALL ARCHITECTURAL DRAWINGS AND SPECIFICATION |
| | IDENTIFICATIONS SHEETS. THE TITLE BLOCK MUST, AT A |
| | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. |
| | PLEASE MAKE SURE ALL INFORMATION IS IN THE TITLE BLOCK |
| | ON EACH SHEET. FAC 61G1-16.004 & FS 481.219, 481.2055. |
| | |
| | 5. THE ADDRESS OF THE BUILDING SHALL BE INDICATED ON |
| | THE PLANS. SECTION 106.1.1. |
| | |
| | REVIEW BY KEN STEVENS |