| Plan Review Notes For Permit 06120592 |
| Permit Number |
06120592 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-02-03 09:06:43 | DENIED; | | | 1. SEE ELECTRICAL PLAN REVIEW NOTES #1 AND #3. | | | 2. PAGE P0.1 PLUMBING NOTE # 11 PLEASE CHANGE NOTE | | | SINCE THE AREA ABOVE THE DROP CEILING IS A PLENUM TO | | | READ NO PVC PERMITED. PIPING MATERIAL TO BE CAST IRON | | | OR COPPER DWV TYPE. | | | 3.PREVIOUS NOT #3 FROM LAST REVIEW, THE WATER HAMMER | | | ARRESTOR TO BE INSTALLED PER MANUFACTURE'S INSTALLATION | | | INSTRUCTIONS, AS CLOSE TO THE SOURCE (FIXTURE) AS | | | POSSIBLE. ONE RISER DIAGRAM MARKED IN RED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|