| Plan Review Notes For Permit 06120592 |
| Permit Number |
06120592 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-16 07:42:48 | DENIED; | | | 1.ADD MISSING INFORMATION TO TITLE BLOCK. SEE | | | ELECTRICAL PLAN REVIEW NOTES 1 & 2. | | | 2.BREAK SINK MUST COMPLY TO THE FBC-2004 BUILDING | | | CHAPTER 11 ACCESSIBILITY CODE. THE ELEVATION (4) PAGE | | | A-06 DOES NOT COMPLY. | | | 11-4.24.2 HEIGHT OF SINK IS 34". | | | 11-4.24.3 KNEE CLEARANCE 27" HIGH, 30" | | | WIDE, AND 19" DEEP. (NO CABINET DOORS) | | | 11-4.24.4 DEPTHMAX 6 1/2" DEEP. | | | 11-4.24.5 CLEAR FLOOR SPACE 30 X 48 SHOW | | | ON FLOOR PLAN. | | | 11-4.24.6 INSULATE EXPOSED PIPES. 3.WATER | | | RISER, WATER HAMMER ARRESTOR TO BE INSTALLED PER | | | MANUFATURE'S SPECS,CLOSE TO THE SOURCE (SHOW AT | | | BOTTOM OF DROP) | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|