| Date |
Text |
| 2008-07-24 09:20:02 | ** DENIED REVIEW ** |
| | |
| | ** THERE ARE COMMENTS WHICH COME FROM PREVIOUS REVIEW |
| | COMMENTS HOWEVER THEY ARE NEW BASED ON INFORMATION NOW |
| | ON PLANS. |
| | THERE ARE ALSO SOME REPEAT COMMENTS |
| | |
| | 1) NOTE: PLEASE SEE THE NEW SERVICE ENTRANCE CONDUCTORS |
| | WHICH ARE NOW BEING SHOWN ARE NOT COMPLETE. NO CONDUIT |
| | SIZE IS SHOWN. THE REVIEW FOR CODE COMPLIANCE FOR |
| | CONDUIT FILL CAN NOT BE DONE. (TABLE 9) |
| | |
| | 2) NOTE: PLEASE ALSO SEE THE NEW SERVICE ENTRANCE |
| | CONDUCTORS DO NOT MEET THE MINIMUM SIZE REQUIRED PER |
| | 240.4B FOR DEVICES OVER 800AMPS. |
| | PLEASE ADJUST. 310.16 |
| | |
| | 3) NOTE: PLEASE SUPPLY AIC RATING OF THE 1200AMP MAIN |
| | AS PREVIOUSLY REQUESTED. |
| | 110.9. |
| | PLANS NOTE AIC RATING OF PANELS AND BREAKERS HOWEVER |
| | DOES NOT INDICATE MAIN RATING. |
| | |
| | 4) NOTE: PLEASE SEE UNIT B ON E-3 WHICH IS SHOWING SD |
| | FOR SMOKE DETECTOR. THIS CAN BE REDLINED AND DOES NOT |
| | NEED TO REPRINT SHEETS AT THIS TIME. |
| | |
| | |
| | |
| | IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |