| Plan Review Notes For Permit 06120586 |
| Permit Number |
06120586 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-12-03 18:53:36 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | 4. OK | | | | | | 5. SUBMIT WATER RISER DIAGRAMS FOR EACH UNIT TYPE. SHOW | | | ALL PIPE SIZES, VALVES AND WATER HAMMER ARRESTORS | | | REQUIRED BY SECTION 604.9. (WASH MACHINES, DISH | | | WASHERS, & ICE MAKERS). WATER HAMMER ARRESTORS SHALL BE | | | LOCATED IN AN "EFFECTIVE RANGE", (NOT IN THE CEILING), | | | PER PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS. | | | SECTION 106.3.5.1.3(3)(13). | | | ****RESPONSE NOTED, BUT THE RISER FOR BOTH UNITS "A" | | | &"B" BOTH SHOW THE WATER LINE AS IT ENTERS INSIDE THE | | | BUILDING CHANGING TO 1/2" THEN CHANGES TO 1" TO THE | | | HEATER ETC. PLEASE CLARIFY. ALSO SHUT OFF VALVES SHALL | | | BE INSTALL ON THE SUPPLY LINE TO EACH HOSE BIBB. | | | SECTION 606.2(2). | | | | | | 6. OK | | | 7. OK - INFORMATIONAL | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|