| 2007-11-29 12:29:06 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE KNOW AS STATED ON PREVIOUS REVIEW AS THERE |
| | WERE CHANGES WHICH WERE NEEDED AND ITEMS NOT SUBMITTED |
| | ON PREVIOUS PLANS THERE MAY BE NEW COMMENTS GENERATED |
| | ON THE 2ND REVIEW. |
| | ** PLEASE SEE THESE ARE COMMENTS BASED ON THE PLANS |
| | SUBMITTED AND SOME ITEMS FROM PREVIOUS REVIEW WHICH |
| | STILL NEED TO BE ADDRESSED ALONG WITH NEW COMMENTS. |
| | |
| | |
| | 1) NOTE: PLEASE SEE AS MENTIONED ON PREVIOUS REVIEW |
| | NOTE # 27 THE ADDRESS WAS YET TO BE DETERMINED AND LOOK |
| | FOR COMMENTS FROM THE ADDRESSING REVIEWER. |
| | PLEASE SEE THE NEW ADDRESS OF 1810 EMBASSY DR WAS |
| | GENERATED. AS THESE ARE NOT FEE SIMPLE TOWNHOUSES AND |
| | PLANS HAVE HAD CHANGES INDICATING THIS, PLEASE ADJUST |
| | ADDRESS IN TITLE BLOCKS TO 1810. |
| | |
| | 2) NOTE: PLEASE SEE AS PREVIOUSLY MENTIONED IN NOTE #2, |
| | PLEASE BE SURE ALL SMOKE ALARMS MEET NFPA-72 11.8.3 |
| | WHICH REQUIRES ALL SMOKE DEVICES TO BE A MINIMUM OF 3FT |
| | FROM BATH DOORS AND 20FT FROM COOKING APPLIANCES. THERE |
| | ARE EXCEPTIONS FOR COOKING APPLIANCES IF DEVICE IS OF A |
| | PHOTO-ELECTRIC TYPE AND/OR RESETTING TYPE. |
| | PLEASE SEE UNIT A MASTER BEDROOM FOR EXAMPLE. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS NOTES # 3, #4 AND #10. |
| | PLEASE SEE THERE ARE STILL SOME AREAS WHERE SOME GFI |
| | RECEPTACLES DO NOT MEET 210.52C1-5 AND 210.8A6. |
| | PLEASE SEE E-2 UNIT A, ISLAND FOR ONE EXAMPLE. (GFI) |
| | PLEASE SEE E-2 UNIT A,PENINSULAR AND SEPARATE SPACES |
| | AND COUNTER SPACE FOR EXAMPLE. |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS NOTE #8 FOR LISTING OF ALL |
| | RELEVANT CODES WHICH WERE REQUIRED TO BE ADJUSTED AND |
| | PLACED ON PLANS. |
| | RESPONSE WAS THAT ALL CODES WERE ADDED TO A AND SHEET |
| | E-4, WHICH WAS OK AND CORRECT HOWEVER PLEASE SEE E-2 |
| | AND E-3 AS THE 2002 NFPA-70 ( NEC) IS STILL REFERENCED |
| | IN NOTES. |
| | PLEASE ADJUST. |
| | |
| | 5) NOTE: PLEASE KNOW AS MENTIONED IN PREVIOUS REVIEW |
| | NOTES #11,12 ETC THE SERVICE WAS CHANGED FROM PREVIOUS |
| | PLANS AND NEW COMMENTS ARE NOW BEING MADE. |
| | PLEASE SEE THE FOLLOWING COMMENTS FOR SERVICE RISER: |
| | NOTES 6-11 |
| | |
| | 6) NOTE: PLEASE SEE MISSING CONDUITS FROM FPL TO |
| | SERVICE. AS FPL DOES NOT INSTALL THESE CONDUITS, THESE |
| | FALL UNDER THE NEC AND SIZING REQUIREMENTS FOR |
| | SERVICE. |
| | ***IMPORTANT: PLEASE VERIFY WITH THE FPL SERVICE |
| | PLANNER THAT THE SERVICE ENTRANCE CONDUCTORS ARE |
| | ACTUALLY GOING TO BE PULLED IN AND INSTALLED BY FPL. |
| | ALMOST ALL PROJECTS WHERE AN ON-SITE TRANSFORMER IS |
| | BEING INSTALLED BY FPL THE CONDUITS AND CONDUCTORS |
| | INCLUDING SERVICE ENTRANCE CONDUCTORS FROM SERVICE TO |
| | TRANSFORMER ARE BEING REQUIRED TO BE INSTALLED BY THE |
| | ELECTRICAL CONTRACTOR AND WILL BE THE RESPONSIBILITY OF |
| | THE OWNER. PLEASE KNOW AS MENTIONED ABOVE, IF CONDUITS |
| | AND CONDUCTORS ARE INSTALLED BY ELECTRICAL CONTRACTOR, |
| | THESE WILL BOTH FALL UNDER THE NEC AND ARE NEEDED TO BE |
| | SHOWN ON PLANS/SERVICE RISER. |
| | PLEASE OBTAIN LETTER FROM THE SERVICE PLANNER IF THESE |
| | WILL BE INSTALLED BY FPL. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE THE CONDUIT SIZE IS MISSING FOR |
| | FEEDERS TO UNITS AND ARE UNABLE TO REVIEW AT THIS TIME |
| | FOR CODE COMPLIANCE. PLEASE SEE CONDUIT FILL TABLE IN |
| | CHAPTER 9 (C). |
| | FBC 106.3.5.1.2 |
| | |
| | 8) NOTE: PLEASE SEE THE CONDUIT FOR HOUSE PANEL IS TOO |
| | SMALL FOR CONDUCTORS ARE SHOWN. NO CONSIDERATION HAS |
| | BEEN GIVEN FOR LENGTH AT THIS TIME. |
| | PLEASE ADJUST SIZE OF CONDUIT. |
| | FBC 106.3.5.1.2 |
| | |
| | 9) NOTE: PLEASE SEE THE SERVICE METER CENTER IS BEING |
| | SHOWN AS 1160AMPS WHICH IS NOT A STANDARD SIZE PER |
| | 240.6. PLEASE PROVIDE THE STANDARD SIZE OF EQUIPMENT. |
| | FBC106.3.5.1.2 |
| | |
| | 10) PLEASE SEE THE METER CENTER DOES NOT INDICATE ANY |
| | MAIN AS REQUIRED PER 230.70, 230.71. |
| | FBC 106.3.5.1.2 |
| | |
| | 11) PLEASE SEE NO AIC RATING(S) FOR MAINS AND BREAKERS |
| | ARE INDICATED AS REQUIRED.110.9, FBC 106.1.2, |
| | 106.3.5.1.2 |
| | |
| | 12) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE # 23 |
| | REQUESTED COMPLETED LOAD CALCULATIONS WHICH WERE |
| | SUBMITTED HOWEVER PLEASE SEE 422.13 AS THE WATER |
| | HEATERS ARE NOW CONSIDERED A CONTINUOUS LOAD UNDER THE |
| | NEW CODE AND IS REQUIRED TO BE FIGURED AT 125%. |
| | PLEASE ADJUST CALCULATIONS. |
| | FBC 106.3.5.1.2 |
| | |
| | 13) NOTE: PLEASE SEE PREVIOUS NOTES #14 AND #28 AS |
| | ROOMS ARE AREAS NEEDED TO BE SHOWN ON PLANS, |
| | SPECIFICALLY DINING AREAS/ROOMS. PLEASE SEE AS |
| | PREVIOUSLY NOTED THE DINING AREAS AND/OR ROOMS SHALL BE |
| | ON ONE OR MORE OF THE SMALL APPLIANCE CIRCUITS. |
| | PLEASE SEE E-3 UNIT B OPTION AS THE DINING RECEPTACLES |
| | ARE BEING SHOWN ON A GENERAL LIGHTING CIRCUIT WHICH IS |
| | NOT PERMITTED. |
| | |
| | 14) NOTE: PLEASE SEE THE LOCATION OF THE ELECTRICAL |
| | SERVICE IS OF CONCERN. PLEASE SEE BASED ON THE SIZE OF |
| | SUCH EQUIPMENT AND BASED ON THE SCALE AND LOCATION AS |
| | SHOWN ON PLANS THERE SEEMS THERE WILL BE AN ISSUE FOR |
| | MINIMUM WORKING CLEARANCES AND PROTECTION OF EQUIPMENT. |
| | AS THE LOCATION HAS A DRIVEWAY/PARKING AREA IS RIGHT IN |
| | FRONT OF EQUIPMENT, NOT ONLY WILL THE EQUIPMENT REQUIRE |
| | MINIMUM CLEARANCES, BUT ALSO PROTECTION BY BOLLARDS TO |
| | PREVENT DAMAGE. PLEASE PROVIDE MINIMUM CLEARANCES, |
| | BOLLARD DETAIL, SITE DETAIL INCLUDED WITH THE ELEVATION |
| | DETAIL. |
| | PLEASE SEE BASED ON SCALE THE EQUIPMENT AS THIS IS VERY |
| | LARGE IN NATURE MAY PROTRUDE INTO DRIVE AREA. |
| | 110.26 |
| | |
| | 15) NOTE: PLEASE PROVIDE INFORMATION AND ELECTRICAL |
| | PLANS FOR HOUSE PANEL AND EQUIPMENT. |
| | PLEASE SEE THAT NO PANEL SCHEDULE WAS SUBMITTED WITH |
| | OVER CURRENT PROTECTION, CIRCUITS, CONDUCTORS ETC. |
| | PLEASE SEE NO ELECTRICAL PLANS WERE SUBMITTED SHOWING |
| | LOCATION OF ELECTRICAL ON HOUSE PANEL. |
| | FBC 106.3.5.1.2 |
| | NEC 2005 240.4, 310.16 ETC |
| | |
| | 16) NOTE: PLEASE SEE 408.4, PLEASE PROVIDE MORE |
| | SPECIFIC DESIGNATIONS ON CIRCUITS AS SHOWN ON PANEL |
| | SCHEDULES. |
| | PLEASE SEE THE USE OF * GENERAL LIGHTING* SHOULD SHOW |
| | OR INDICATE THE ROOMS AND AREAS IN WHICH THESE CIRCUITS |
| | FEED. FOR EXAMPLE: BEDROOM #2 LIGHTING, LIVING ROOM |
| | LTS/RECEPTS ETC. |
| | THIS WAS A CHANGE IN THE 2005 CODE WHICH REQUIRES MORE |
| | SPECIFIC DETAILS. |
| | PLEASE ALSO SEE THE CIRCUITING AS SHOWN FOR UNIT *B* |
| | INDICATES CIRCUITING TO PANEL *A*. |
| | THESE DESIGNATIONS SEEM TO BE A MISPRINT AND SHOULD BE |
| | *B-3*, B27, B21 ETC. |
| | 408.4. |
| | FBC 106.3.5.1.2, 106.5 |
| | |
| | 17) NOTE: PLEASE SHOW ON SITE ELECTRICAL PLANS THE |
| | LOCATIONS OF ALL CONDENSING UNITS, DISCONNECTS AND GFI |
| | RECEPTACLES. |
| | 440.11, 110.26, 210.63, 210.8 |
| | FBC 106.1.2 |
| | |
| | 18) NOTE: PLEASE SEE PREVIOUS NOTE #24 FOR 210.52. |
| | THERE IS STILL SOME RECEPTACLES MISSING AND NOT LOCATED |
| | AS REQUIRED PER 210.52. |
| | PLEASE SEE SOME OF THESE ARE REDLINED ON ONE OF THE SET |
| | OF PLANS. |
| | PLEASE SEE MISSING RECEPTACLES WITHIN 6FT OF DOORWAY |
| | OPENINGS. |
| | PLEASE ALSO KNOW THAT PERMANENT RAIL AREAS ARE |
| | CONSIDERED WALL SPACE. |
| | |
| | 19) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS |
| | ONLY A NOTICE GIVEN AT THIS TIME. |
| | |
| | ** ONCE AGAIN AS THERE ARE SOME ITEMS NOT YET SUBMITTED |
| | FOR REVIEW THERE MAY BE NEW COMMENTS GENERATED ON THE |
| | NEXT REVIEW AS THESE ITEMS CAN NOT BE REVIEWED AT THIS |
| | TIME. |
| | |
| | *** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |